Specifications
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M iLux Integrated Lighting System
Operations Guide – DOC. 6347G iLux Integrated Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M • 61
ALL = ALL Light zones
Reply packet:
[ILUX] LZ [X|ALL] LVL [LEVEL1] [….] [LEVEL6]
LEVEL x = 0–100 (for light zone 1 through 6)
Light Zone Lower or Raise Command
The specified lighting load (or all loads) ramps up or down at the specified rate. The
FADERATE is specified as the time it takes to raise or lower the full range (from
full off to full on or full on to full off). For example, if 5 seconds are specified, it
takes 5 seconds to ramp from off to full on and 2.5 seconds to ramp from 50% level
to full on. If FADERATE is not specified, or if the specified zone is on a slave iLux
unit, the internal fade rate is used.
Syntax: [ILUX] LZ [X|ALL] [UP|DN] [FADERATE]
X = 1–6 light zone
ALL = All Light zones
UP = Raise light level
DN = Lower light level
FADERATE = 0–594000 in 0.01 second steps (e.g. 100 = 1 seconds)
Light Zone Stop Command
The following command is used to stop the light zone control:
Syntax: [ILUX] LZ [X|ALL] [STOP]
X = 1–6 light zone
ALL = All Light zones
STOP = Stop light level
Light Zone Toggle Command
If the specified lighting load is on (or any zone is on, when “all” is specified), the
lighting load ramps down at the specified rate. If the specified lighting load is off (or
all zones are off, when “all” is specified), the lighting load ramps up at the specified
rate. The FADERATE is specified as the time it takes to raise or lower the full range
(from off to full on or from full on to off. For example, if 5 seconds are specified, it
takes 5 seconds to ramp from off to full on and 2.5 seconds to ramp from 50% level
to full on. If FADERATE is not specified, the internal fade rate will be used.
Syntax: [ILUX] LZ [X|ALL] TOG [FADERATE]
X = 1–6 light zone
ALL = All light zones
FADERATE = 0–594000 in 0.01 second steps (e.g. 100 = 1 seconds)
Light Zone Programming
Commands
Light Zone Lower Limit Command
The following command is used to get light zone min limit. This command is not
supported for slave CLS-C6 controllers:
Syntax: M LZ [X|ALL] MIN ?
X = 1–6 light zone