Specifications

iLux Integrated Lighting System Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
60 iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M Operations Guide DOC. 6347G
RS-232 Command Table (Continued)
COMMAND SYNTAX REPLY
DESCRIPTION CATEGORY
Occupancy Read
occupancy
state
[ILUX] OC ? [ILUX] OC [STATE]
Photocell Read
Photocell
active state
[ILUX] PH [X|ALL] ACTIVE
?
[ILUX] PH [X] ACTIVE
[STATE1][…][STATE6]
Version Read version
number
[ILUX] VER ? [ILUX] VER [ID STRING]
NOTE: Command and response parameters are separated by blank spaces.
Adding C2N-IO Device to CLS-C6
To add a C2N-IO module to CLS-C6, connect the module to the CLS-C6 Cresnet
slave network port and run auto-discovery from CLS-C6 front panel. CLS-C6 adds
the device to its network list. The CLS-C6 then polls and configures the C2N-IO
serial port.
The C2N-IO serial port baud rate settings are 9600, 8 data bits, 1 stop bit,
XON/XOFF disabled, and RTS/CTS disabled.
Echo Control Command
This command is used to enable/disable character echo.
Syntax: [ILUX] Echo [ON|OFF]
Light Zone Commands
Light Zone Operation
Commands
Light Zone Level Command
The following command is used to set the light zone levels:
Syntax: [ILUX] LZ [X|ALL] LVL [LEVEL] [FADETIME]
X = 1–6 light zone
ALL = ALL light zones
FADETIME = 0–594000 in 0.01 second steps (e.g. 100=1 seconds)
Level:
LEVEL IN PERCENT DESCRIPTION
0 Level off
1 to 100 Level On
Light Zone Level Recall Command
The following command is used to get the light zones level:
Syntax: [ILUX] LZ [X|ALL] LVL?
X = 16 light zone