Serial Command String Format to Third Party Controllers.
ILUX CONTROLLER COMMAND PAR1…X CARRIAGE
RETURN
LINE FEED
Refer to the “iLux
Controller Code Table”
below for a list of
available options.
Refer to the “RS-232
Command Table” on
the following page
which provides a
description of
available commands
and the required
syntax.
A list of available
variables that
can be entered
into the
command. The
brackets should
be removed
from the
command.
[Par1]
[……..]
[Parx]
0Dh 0Ah
Serial Command String Format From Third Party Controllers.
STATUS NUM CARRIAGE
RETURN
LINE FEED
Response packet type 1
This response packet is returned if command fails or is invalid
ERROR X=Error
Code
0Dh 0Ah
Response Packet Type 2
This response packet is returned if command requires status or reply packet
from the controller
Response Par1–Parx 0Dh 0Ah
Response Packet Type 3
This response packet is returned if there was no packet error and a status or
reply packet response is not required
OK 0Dh 0Ah
iLux Controller Code Table
CONTROLLER
CODES
DESCRIPTION
M Commands the iLux Master Controller
S1S8 Commands the iLux Slave Controller 1 through 8
When entering a command to control the iLux replace [ILUX] in the “RS-232
Command Table” with the specified controller code listed in the “iLux Controller
Code Table” above. Possible entries are: M, S1, S2, S3, S4, S5, S6, S7, or S8.
Refer to the following “RS-232 Command Table” for a list of possible commands
that can be sent to the CLS-C6. Information contained within braces (e.g. [ILUX]
or [X|ALL]) should be replaced with the appropriate command minus the braces.
To turn the echo command on for a master controller ([ILUX] ECHO ON|OFF)
enter M ECHO ON.
When a lighting load is declared as unaffected in iLux Designer, the text console
reports “– –” as the value.