Specifications

iLux Integrated Lighting System Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
56 iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M Operations Guide DOC. 6347G
Appendix C: RS-232 Commands
Connect the third party controller to the serial port of the C2N-IO. Connect the
C2N-IO to the CLS-C6s Local Devices G Z Y 24. ASCII commands received by
the serial converter module are sent to the CLS-C6 slave Cresnet port. The CLS-C6
Cresnet serial packets are forwarded as ASCII strings to the third party controllers.
Only one C2N-IO device is allowed on the local Cresnet network. The Cresnet ID
for the C2N-IO should be set to 00 so that the iLux can assign D5 when auto-
discovery is run.
NOTE: When connecting the C2N-IO serially to the PC ensure proper wiring. The
Tx pin of the C2N-IO serial connector must connect to the Rx pin of the serial
connector on a PC. Additionally, the Rx pin of the C2N-IO serial connector must
connect to the Tx pin of the serial connector on a PC, and then ground.
NOTE: If the PC is connected to the CLS-C6 and the C2N-IO (serially) at the same
time, then choose a different port for the C2N-IO since the serial connection is not
shared (COM1, COM2, … COM6). This can be performed in the Crestron Toolbox
Address Book when selecting the communications settings for the C2N-IO.
Command Format
All packets from the third party equipment shall be in ASCII character set range 0 to
127. Extended ASCII characters higher than 127 are not supported. All command
and reply packets for the third party controller between the CLS-C6 and C2N-IO
devices are in Cresnet serial packet type 0x12 format. The serial packet payload
contains the ASCII command or reply strings from the third party controllers.
Serial Port Configuration Packet to C2N-IO
CRESNET
ID
LENGTH CMD STRING
NUMBER
PAYLOAD
DATA 0..X
1-Byte 1-Byte 1-Byte 1-Byte x-Bytes
XX 07 12 80 00 25 00 00 00
Refer to the “Cresnet II Packet” document for more information on this command.
Serial Packets Between CLS-C6 and C2N-IO
CRESNET
ID
LENGTH CMD STRING
NUMBER
PAYLOAD
DATA 0..X
1-Byte 1-Byte 1-Byte 1-Byte x-Bytes
XX LL 0x12 0x80 00..XX
Refer to the Cresnet protocol specifications for more details on this packet.