Digital Feedback Joins (from CLS-C6 to Touch Screen) (Continued)
JOIN DESCRIPTION
6142 Load 6 is on
61446149 Load 16 is set to be non-dim
6150/6151/6152 Shade group 1 moving/last dir. Open/last dir. Close
6160/6161/6162 Shade group 2 moving/last dir. Open/last dir. Close
6170/6171/6172 Shade group 3 moving/last dir. Open/last dir. Close
6180/6181/6182 Shade group 4 moving/last dir. Open/last dir. Close
6190/6191/6192 Shade group 5 moving/last dir. Open/last dir. Close
6200/6201/6202 Shade group 6 moving/last dir. Open/last dir. Close
6205/6206 Last Scene Master Raise/Lower feedback
6207/6208 All Lights Master Raise/Lower feedback
6209/6210 On Scene Master Raise/Lower feedback
62116240 Scene 115 Master Raise/Lower feedback
6245 In Setup mode
6248 Programming the On Scene
6249 Programming the Off Scene
6250 Programming Scene by number
62543959 Lighting load 16 is in Edit Scene
62606265 Shade group 16 is in Scene
6266 Edit Scene is locked
6269 Fade time shown is in minutes
6270 Motion activity
6271 Function activity
6272 Current occupancy state
6274 Entry scene enabled
6278 Exit scene enabled
62806311 Not supported (note: external button fb is sent at same join
number)
6312
In Override mode
6313
In Load Shed mode
63206355 Partition 136 is open (rooms are combined)
6358 Photocell enable feedback light zone 1
6359 Photocell enable feedback light zone 2
6360 Photocell enable feedback light zone 3
6361 Photocell enable feedback light zone 4
6362 Photocell enable feedback light zone 5
6363 Photocell enable feedback light zone 6
6364 Photocell active feedback light zone 1
6365 Photocell active feedback light zone 2
6366 Photocell active feedback light zone 3
6367 Photocell active feedback light zone 4
6368 Photocell active feedback light zone 5
6369 Photocell active feedback light zone 6