Specifications
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M iLux Integrated Lighting System
Operations Guide – DOC. 6347G iLux Integrated Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M • 45
The iLux Designer help file includes a table indicating all the reserved joins
supported by the touch screens.
NOTE: These are not the standard reserved joins, but are the join numbers
understood by the CLS-C6 for performing various actions.
Joins
Digital Command Joins
External functions and their feedbacks are only supported by the master iLux. The
slave CLS-C6(s) does not support external functions.
Programmable joins 1 through 20 and partition joins and their feedback are only
supported for the master CLS-C6.
Digital Command Joins (from Touch Screen to CLS-C6)
JOIN DESCRIPTION
1–20 Programmable via iLux Designer (no feedback)
100/101/
102–116
Recall for Off Scene/On Scene/ Scene 1–15
133/134–148 Turn off loads in On Scene/ Scene 1–15
198/199–213 Toggle On Scene/Scene 1–15
232–243 Raise/Lower load 1–6 (z1 up, z1 dn, z2 up...)
244 Shade group 1 full open
245 Shade group 1 full close
246 Shade group 1 full stop
247 Shade group 1 open momentary
248 Shade group 1 close momentary
249 Shade group 1 open jog
250 Shade group 1 close jog
251 Shade group 1 full open /momentary open
252 Shade group 1 full close /momentary close
253 Shade group 1 full open/stop/close/stop
254–263 Shade group 2 control
264–273 Shade group 3 control
274–283 Shade group 4 control
284–293 Shade group 5 control
294–303 Shade group 6 control
304 Last Scene Master Raise
305 Last Scene Master Lower
306/307 All Lights Master Raise/Master Lower
308/309 On Scene Master Raise/Master Lower
310/311...
338/339
Scene 1 Raise/Lower ... Scene 15 Raise/Lower
344 Quick save current light levels to scene specified in analog join
32 (no change to unaffected loads).
348/349 Program On Scene/Off Scene
(Continued on following page)