Specifications
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M iLux Integrated Lighting System
Operations Guide – DOC. 6347G iLux Integrated Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M • 37
To exit Lights mode, press the Lights button again (or press Cancel) and the LED
goes off. The unit returns to Standard mode. (Also, if no adjustments are made
within 1 minute, the unit reverts to Standard mode.)
Pressing the Shades button automatically exits Lights mode and enters Shades mode.
Shades Mode
Shades mode allows manual control any of the six shade groups. To enter Shades
mode, raise the cover and press the Shades button. The corresponding LED lights
and the six function buttons can be used to adjust shade groups 1 through 6. Any
scenes that are currently in the middle of a fade immediately go to their target value.
The seven white front panel LEDs go out. In this mode, these LEDs do not reflect
the feedback status of the associated scenes. When the unit is returned to Standard
mode, these LEDs return to their standard feedback indication.
• The six function buttons act as open/stop/close/stop (rocker type) for each
of the corresponding six shade groups.
• Operation is as described for the Shade Control button type in Standard
mode. Refer to “Button Types” on page 32 for more information.
• For shade groups with C2N-SSC-2 controllers see below:
⇒ While in Shades mode, the bar graphs indicate the current shade
position.
⇒ The 2-digit display indicates the current percentage level of the shade
group being adjusted (CL, 01 to 99, OP).
⇒ The 2-digit display disappears (goes blank) 3 seconds after the shade
stops moving (due to either a stop command or reaching a limit of
travel).
NOTE: The 2-digit display only shows the shade level when being
adjusted from front panel buttons in Shades mode or scene
programming. It does not display when adjusting levels from a remote
panel or Cresnet.
• For shade groups with C2N-SDC or C2N-SDC-DC controllers see below:
⇒ Bar graphs initially display nothing while a shade is not moving. While
the shade is moving open, the bar graph LEDs scroll in an upward
direction. While moving closed, the bar graph LEDs scroll in a
downward direction. When the shade is stopped or the maximum time
is reached, the bar graph turns off.
⇒ The 2-digit display shows “OP” or “CL” accordingly.
⇒ The up/down button acts as a shades master when in Shades mode, no
matter what function is programmed for it. Pressing the top while the
shade is stopped sends it to full open; pressing the bottom while the
shade is stopped sends it to full close; pressing anything while the
shade is moving stops it; and pressing both while the shade is stopped
causes the shade to move in the opposite direction.
⇒ The ON and OFF buttons on the CLS-C6 unit operate normally while
in Shades mode. The same is true for all scene recall or scene toggle
functions triggered by remote panel or Cresnet command.
⇒ Inputs/commands from any remote devices, motion detector, and
Cresnet control system are processed as usual while in Shades mode. If