Specifications
iLux Integrated Lighting System Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
34 • iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M Operations Guide – DOC. 6347G
IR Receiver
Functions can also be triggered through the built-in RC5 IR receiver using the
optional CLS-IRHT8 remote or a third-party remote. Refer to “Appendix G: RC5
Code Expansion” on page 84 for details.
Occupancy Sensing
Occupancy sensing utilizing the built-in sensors (CLS-C6) may have specific actions
specified for entry and exit. Either or both of these may be disabled. A limited
number of actions are available when programmed locally; more options are
available when programmed using the iLux Designer program.
If motion is detected, or some other activity takes place, a room is considered
occupied. If no activity takes place for a specified time (default is 30 minutes), the
room is considered unoccupied.
When the state of the room changes from occupied to unoccupied, the exit function
(if enabled) is executed. When the state of the room changes from unoccupied to
occupied, due to motion detection, the entry function (if enabled) is executed. When
the state of the room changes from unoccupied to occupied, due to a button press or
the receipt of a command, no function is executed.
NOTE: In systems with multiple CLS-C6 units that have the motion sensor function
enabled on any of the units, it is important to set the motion sensor timeout of each
unit to the same value. Otherwise, operation may not be as expected.
External partition sensors (provided by others) connected via the GLS-SIM product
enable additional actions such as room combining. Refer to “Appendix F: Room
Combining” on page 81 for additional details.
Setting a GLS-SIM to the designated Cresnet ID (0xC0 or 0xC1) causes this
GLS-SIM to behave like an external occupancy sensor. Both inputs on the GLS-SIM
are treated identically, allowing a total of up to six occupancy sensors (three wired in
parallel on each input). Refer to the GLS-SIM Operations & Installation Guide (Doc.
6768) at
www.crestron.com/manuals for detailed information.
Any external sensors are internally OR'd together with the internal motion sensor, if
present.
The timeout property, which is defined in iLux Designer, does not affect external
sensors in any way. This property applies only to the internal sensor in the iLux,
when present. External sensors are responsible for providing their own timeout.
Override Mode
CLS-C6 supports an Override mode, which can be triggered by a GLS-SIM or
DIN-IO8. When Override mode is engaged, a special Override scene is recalled and
all local functionality of the iLux, and associated keypads, are locked out. By default,
the Override scene is all lights at 100% and supports a fade time of only 0 seconds.
The Override scene can be programmed locally on the iLux by entering scene
programming (Sc) option and then cycling through the available scenes until "Or"
appears on the display.
The Override scene cannot be set so that all loads are off.
When Override mode is disengaged, all loads revert to their previous values. While
in Override mode, all slave units are placed into Override mode as well, regardless
of the room combining status.