Specifications
iLux Integrated Lighting System Crestron CLS/CLSI-C6 & CLS/CLSI-C6M
24 • iLux Integrated Lighting System: CLS-C6/C6M & CLSI-C6/C6M Operations Guide – DOC. 6347G
Photocell Response Time (Pr)
This setup option is used to adjust the lights’ response time to a change in the
photocell reading. Valid values are 10 seconds, 30 seconds, 1 minute, 2 minutes, and
5 minutes. The default value is 1 minute.
To adjust the response time of the photocell, see below:
• Enter Setup mode and scroll to the “Pr” option (using the and buttons).
Press either the top or bottom portion of the raise/lower button. The 2-digit
display indicates the response time.
• Use the and buttons (located next to Save/Cancel) to increase or
decrease the response time.
• Press Save to save the new setting or Cancel to retain the original setting.
NOTE: The CLS-C6 temporarily utilizes a faster response time when there
are rapid changes in light (such as when shades or blinds are opened or
closed). If daylight in the room has increased, the response time is increased
to 10 seconds. If daylight in the room has decreased, the response time is 2
seconds. Under normal operation, the CLS-C6 implements a gradual
response time.
Restore Factory Defaults (Fd)
This procedure is used to restore all settings to their factory defaults.
1. First enter Setup mode and then scroll to the “Fd” option (using the and
buttons). Then press the up/down button (top, bottom, or both) and hold for
5 seconds.
2. This procedure is locked in and the Save LED flashes. (If the button is
released before 5 seconds are up, nothing happens.) Press Save and all
configuration items are set to their factory default values. (Press Cancel and
the unit exits Setup mode without changes.) The factory default
configuration does not include any remote devices. To re-initialize remote
devices, run auto-discover after this function. Running the factory default
function does modify the Cresnet ID of the CLS-C6.
3. The save process may take a few seconds. During this time, the Save LED
is lit steadily and the 2-digit display shows “– –”. When the process is
complete, the LEDs extinguish.
Refer to “Appendix C: RS-232 Commands” on page 56 for default values.
Configuring with iLux Designer
The Crestron iLux Designer program software, supplied with all of the CLS-C6
series units, configures the CLS-C6 as an independent, standalone device or as a
network device in a Crestron network control system (Cresnet system).
To configure the CLS-C6 using the iLux Designer, use a direct serial connection as
described in “Establishing Communication” on page 29.
NOTE: Connecting the serial cable to the front panel of the CLS-C6 disconnects the
control system network.
Configuring the CLS-C6 consists of setting the load schedule definition, the shade
group configuration, the scene definitions, the CLS-C6 panel configuration, and
keypad configuration for each CLS-C6 device.