Specifications
Crestron CLS/CLSI-C6 & CLS/CLSI-C6M iLux Integrated Lighting System
Operations Guide – DOC. 6347G iLux Integrated Lighting System: CLS/CLSI-C6 & CLS/CLSI-C6M • 19
• The first mode to be displayed is the current mode.
• When programming from the front panel, exit time cannot be adjusted or
displayed. If exit time has not been changed with iLux Designer or SIMPL
Windows the default is 30 minutes. Scenes to be recalled also cannot be
changed from the front panel. If they have not been changed with iLux
Designer, the Off scene is recalled on exit (if enabled) and On scene is
recalled on entry (if enabled).
• Even if these items are changed with iLux Designer, they can still be
enabled and disabled from the front panel without modifying the specified
scenes or exit time.
• If Cancel is pressed, or Setup mode times out, the previous occupancy
setting is restored. To have the new setting take effect, Save must be
pressed.
NOTE: In mode 0, even though nothing happens locally when occupancy
state changes, the occupancy status is still reported to Cresnet.
This mode can also be used to test the range of the occupancy sensor. While
locked in the “oc.” option, each time motion is sensed, the middle LEDs on
all six bar graphs blink.
Run Auto-Discovery (Ad)
This setup option is used to find which remote devices are on the network, assign
Cresnet IDs to new devices, and assign default functions to new panels and devices.
• To enter this mode, first enter Setup mode and scroll to the “Ad” option
(using the and buttons). Then press the up/down button (top, bottom, or
both) and hold for 5 seconds. The auto-discovery process then starts. (If the
button is released before 5 seconds are up, nothing happens, but “Ad.”
option is locked in.) Once “Ad.” option is locked in, the Cancel button
flashes.
• During auto-discovery, the “Ad.” display flashes. When auto-discovery is
done, the 2-digit display flashes between “Ad.” and “##” where “##” is the
number of devices discovered on the network. The Save button also starts
flashing. Press Save or Cancel.
NOTE: If a C2N-IO (sold separately) is connected to the system, set the
rotary DIP switches to 00 or D5 before auto-discovery is performed. If the
C2N-IO is not configured properly, the CLS-C6 cannot recognize that the
C2N-IO is connected and may result in an error.
• The CLS-C6 keeps a list of all devices on its local network. If the auto-
discovery finds devices that match the list, it does not change anything
about those.
• In addition to initially configuring the system, auto discovery can be used to
add or replace keypads or shade controllers. If adding a device, all
previously assigned devices are not changed. The new device is added and
assigned default functionality, if desired.
• To replace a device (because of defect or color choice), remove the device
and replace with another device of the same type. When executing auto-
discovery, the new device takes on the functionality of the original device.
Use the “bF” option to change functionality, if desired.