Crestron CHV-RSS Remote Slab & Outdoor Temperature Sensor Installation Guide
. Regulatory Compliance As of the date of manufacture, the CHV-RSS has been tested and found to comply with specifications for CE marking and standards per EMC and Radiocommunications Compliance Labelling. Federal Communications Commission (FCC) Compliance Statement CAUTION: Changes or modifications not expressly approved by the manufacturer responsible for compliance could void the user’s authority to operate the equipment.
Crestron CHV-RSS Remote Slab & Outdoor Temperature Sensor Contents Remote Slab Sensor and Outdoor Temperature Sensor: CHV-RSS 1 Introduction ............................................................................................................................... 1 Specifications .............................................................................................................. 2 Physical Description ........................................................................................
Crestron CHV-RSS Remote Slab & Outdoor Temperature Sensor Remote Slab Sensor and Outdoor Temperature Sensor: CHV-RSS Introduction The CHV-RSS is a remote temperature sensor designed for use with select Crestron® thermostats. Ideally suited for concrete slab, under floor, or any outdoor installation, the CHV-RSS is an extremely accurate temperature sensor potted within a rugged waterproof stainless steel sleeve.
Remote Slab & Outdoor Temperature Sensor Crestron CHV-RSS Specifications Specifications for the CHV-RSS are listed in the following table. CHV-RSS Specifications SPECIFICATION Measurement Range Indoor Temperature Outdoor Temperature Accuracy Temperature Accuracy Over Full Range At Room Temperature Connection Enclosure Dimensions Diameter Depth DETAILS 0° to 110° F (-18° to 43° C) -40º to 170º F (-40º to 77º C) ±1° F (0.5° C) ±1° F (0.5° C) +1° F (+0.1 / -0.
Crestron CHV-RSS Remote Slab & Outdoor Temperature Sensor Physical Description This section provides information on the connections, controls and indicators available on the CHV-RSS. CHV-RSS Physical View CHV-RSS Overall Dimensions 0.32 in (8 mm) 2.75 in (70 mm) 20 ft (6 m) Installation Guide – DOC.
Remote Slab & Outdoor Temperature Sensor Crestron CHV-RSS Setup Tile or Wood Floor Installation Crestron recommends the sensor be placed inside a 1/2 inch (13 mm) Electrical Metallic Tubing (EMT) conduit. This allows future sensor replacement, if required. The radius of the bend at the wall should be approximately 8 inches (203 mm), to allow for removal and replacement of the sensor.
Crestron CHV-RSS Remote Slab & Outdoor Temperature Sensor • In very large spaces, two sensors may be used to average the floor temperature. • The sensor should be placed midway between heating elements. Sensor Position (Top View) Heating Pipe or Elements Conduit Midway Between Heating Elements or Pipes Sensor Center of Floor (or 6 ft (1.
Remote Slab & Outdoor Temperature Sensor Crestron CHV-RSS NOTE: In tile floors, ensure a channel is made in the thin-set mortar, just above the subflooring, to properly position the sensor. Outdoor Installation Required Materials (not supplied): • Two wood screw coaxial cable standoffs with insulators • One plastic feedthrough bushing • Silicon adhesive NOTE: Mount in a location away from direct sunlight. NOTE: Sensor should not come in contact with metal objects.
Crestron CHV-RSS Remote Slab & Outdoor Temperature Sensor Outside Wall Mounting Installation Guide – DOC.
Remote Slab & Outdoor Temperature Sensor Crestron CHV-RSS Hardware Hookup CHV-RSS sensors connect to the terminal blocks on the back plate of the CHV-TSTAT, CHV-THSTAT, CHV-TSTATEX, CHV-TSTATEX-FCU thermostats (all sold separately). NOTE: Sensor wiring is non-polarized. NOTE: Up to two CHV-RSS sensors may be connected to a single channel. NOTE: Use a separate run of wire for each sensor.
Crestron CHV-RSS Remote Slab & Outdoor Temperature Sensor Front Plate Removal 3. To connect the sensor(s) to a single channel on the thermostat, wire the CHV-RSS to the RS1 and RSR terminals as shown on the following page. Installation Guide – DOC.
Remote Slab & Outdoor Temperature Sensor Crestron CHV-RSS CHV-RSS (Single Channel) Hookup (Two Sensors Shown) CHV-RSS CHV-RSS 24V Y Z G HUM RHU RSR RSR RS1 RS2 24(C) 24(R) TOP RH RC G Y/Y1 Y2 O B W/W1 W2 NETWORK 4. To connect sensors using two channels on the thermostat, wire up to two devices to the RS1 and RSR terminals, and up to two devices to the RS2 and RSR terminals as shown in the illustration on the following page.
Crestron CHV-RSS Remote Slab & Outdoor Temperature Sensor CHV-RSS (Dual Channel) Hookup (Four Sensors Shown) CHV-RSS CHV-RSS CHV-RSS CHV-RSS Z G 24V Y HUM RHU RSR RSR RS1 RS2 24(C) 24(R) TOP B W/W1 W2 RH RC G Y/Y1 Y2 O NETWORK 5. Note the orientation of the front plate connection pins and reattach the front plate (make sure the front plate snaps in place and no wires are pinched).
Remote Slab & Outdoor Temperature Sensor Crestron CHV-RSS Problem Solving Troubleshooting The following table provides corrective action for possible trouble situations. If further assistance is required, please contact a Crestron customer service representative. CHV-RSS Troubleshooting TROUBLE No signal. POSSIBLE CAUSE(S) Improper connection. Incomplete (open) circuit. CORRECTIVE ACTION Check connection to thermostat (refer to “Hardware Hookup”, which starts on page 8). Check wiring.
Crestron CHV-RSS Remote Slab & Outdoor Temperature Sensor To post a question about Crestron products, log onto the Online Help section of the Crestron Web site (www.crestron.com/onlinehelp). First-time users must establish a user account to fully benefit from all available features. Future Updates As Crestron improves functions, adds new features and extends the capabilities of the CHV-RSS, additional information may be made available as manual updates.
Remote Slab & Outdoor Temperature Sensor Crestron CHV-RSS Return and Warranty Policies Merchandise Returns / Repair Service 1. No merchandise may be returned for credit, exchange or service without prior authorization from Crestron. To obtain warranty service for Crestron products, contact an authorized Crestron dealer. Only authorized Crestron dealers may contact the factory and request an RMA (Return Merchandise Authorization) number.
Crestron CHV-RSS Remote Slab & Outdoor Temperature Sensor This page is intentionally left blank. Installation Guide – DOC.
Crestron Electronics, Inc. 15 Volvo Drive Rockleigh, NJ 07647 Tel: 888.CRESTRON Fax: 201.767.7576 www.crestron.com Installation Guide – DOC. 6229D (2009402) 02.13 Specifications subject to change without notice.