Installation guide
Crestron C2N-DBN12 & C2N-DBF12 Decorator Wall Panels
Operations & Installation Guide - DOC. 6200 Decorator Wall Panels: C2N-DBN12 & C2N-DBF12 • 11
“Set Net ID by TSID” Window
5. Enter either the serial number or TSID number of the device
that requires a change. The list scrolls to and highlights the
device listing. The listing should show the device’s default
Cresnet ID (a.k.a. Net ID).
6. Enter the Cresnet ID that the device should be set to and click
OK. The number you enter should appear on the list.
CAUTION: This function does not prevent you from setting duplicate
IDs. Be sure to check current assignments before entering the desired
Cresnet ID number.
Serial Number to TSID Conversion
This utility is useful in a case where there are multiple devices of the
same type on a network, you need to locate a particular one, you know
the TSID but not the serial number, and your site installation list is based
on device serial numbers. In this (or the reverse) situation, do the
following:
1. Open the Crestron Viewport.