infiNET™ Thermostat Crestron CHV-TSTATRF
SETUP Mode Parameters/Functions (Continued)
PARAMETER/
FUNCTION
MNEMONIC VALID VALUES
DEFAULT
VALUE
Unacquire Gateway UA
Not started (--)
In progress (flashing --)
Finished, success (00)
Finished, failed (E#, where #
represents an error code)
N/A
Check Battery Life bA
Not started (--)
Estimated battery life remaining (0
– 99)
N/A
Restore Factory
Defaults
8
Fd
Not started (--)
In progress (flashing --)
Finished (00)
Button not held long enough (Er)
N/A
Perform Heat Call Test
(Toggle)
H
Not started/Heat call off (--)
Heat call on (on) (also, “H” icon
will turn on)
N/A
Perform Cool Call Test
(Toggle)
C
Not started/Cool call off (--)
Cool call on (on) (also, “C” icon will
turn on)
N/A
Perform Aux Heat Call
Test (Toggle)
A
Not started/Aux call off (--)
Aux call on (on) (also, “A” icon will
turn on)
N/A
Perform Fan Call Test
(Toggle)
F
Not started/Fan call off (--)
Fan call on (on) (also, “F” icon will
turn on)
N/A
Perform Self Test St
Not started (--)
In progress (flashing --)
Finished, self test ok (00)
Finished, self test failed (E#,
where # represents an error code)
N/A
1. This setting will always be disabled when scale is set to “F”.
2. The Offset option permits recalibration of the room temperature sensor. There are reasons why users may want to adjust
the temperature. The selection number is the number of degrees added to or subtracted from the actual temperature. The
range is –9 to +9 degrees (for Fahrenheit) and –5 to +5 degrees (for Celsius). Factory default is 0 degrees offset. This
adjustment changes the actual regulated temperature, not just the display.
3. A lower anticipator setting results in more frequent cycles and faster response (tighter regulation). A higher setting results
in less frequent cycling and slower response (looser regulation).
4. This parameter will always be set to Enabled (Y) for Heatpump or Dual-Fuel Heatpump systems.
5. For systems where no power is available (batteries only), value can be set to “24”.
6. When firmware version is not yet shown, display will be “--”. Each press of the RAISE/LOWER button will cycle to the
next portion of the version number. Three digit values will be indicated by scrolling the number.
7. SIMPL Windows restricts infiNET devices to an ID range of 03-20.
8. To prevent accidentally performing this action, you must press and hold either the RAISE or LOWER button for three
seconds for this function to execute.
System Modes
The MODE button on the CHV-TSTATRF will cycle the unit through all available
System modes in the following order: Off, Heat, Aux Heat Only (for heatpump and
dual-fuel systems), Cool.
The System mode will change upon release of the MODE button and the selected
mode will become operational three seconds after the mode has been entered.
NOTE: System mode will change on release of the MODE button only if no other
button had been pressed at the same time. If another button is pressed while the
MODE button is held down, the System mode will not change.
20 • infiNET™ Thermostat: CHV-TSTATRF Operations & Installation Guide – DOC. 6490