Specifications
99Environmental Automation: Featured Products
Octal Power and Energy Measurement
IC Provides Accurate Data from Power
Distribution Units
78M6618
The 78M6618 measures power from up to eight single-phase power paths, providing
accurate usage data on eight branch circuits. The 32-bit compute engine and
the 21-bit delta-sigma ADC provide accuracy beyond that required for metering
applications. Temperature compensation and precision voltage reference keep
accuracy in specication over the industrial temperature range (-40°C to +85°C).
Benefits
• Provides high-accuracy data on power
draw on up to eight branch circuits
with a single IC
◦ < 0.5% Wh accuracy over 2000:1
current range over temperature
◦ Power factor measurement
◦ Exceeds IEC 62053/ANSI C12.20
standards
◦ Accumulated Wh, kWh, and cost
• Integrated features enable an
enhanced solution at low cost
◦ Integrated LCD driver up to 70 pixels
◦ UART and high-speed slave SPI host
interface options
◦ 19 GPIOs
◦ Programmable alarm thresholds
Featured Products
IA
V3.3A V3.3D
IB
CONVERTER
TEMP
SENSOR
REGULATOR
AC TO DC
POWER SUPPLY
IC
ID
IE
IF
IG
IH
VA
VB
V1
DC
POWER FAULT
GNDA
+ -
GNDD
V
BAT
V2.5
TX
TX
OPT_TX
OPT_RX
XIN
32kHz
XOUT
78M6618
UARTs
I
2
C
SPI
TIMERS
RTC
OSC/PLL
RAM
COMPUTE
ENGINE
FLASH
VREF
80515
MPU
ICE
COMPARATOR
DIO[1:19]
SEG[1:35]
RELAY DRIVERS, 7-SEG, ETC.
(OPTIONAL)
BATTERY
(OPTIONAL)
HOST µC,
ADDITIONAL 6618s
HOST µC,
ADDITIONAL 6618s
EEPROM
(OPTIONAL)
CT-1
CT-2
OUTLET1
OUTLET2
CT-3
OUTLET3
CT-4
OUTLET4
CT-5
CT-6
OUTLET6
CT-7
OUTLET7
CT-8
OUTLET8
LIVE
NEUTRAL
OUTLET5
LIVE
NEUTRAL
Typical application circuit for 78M6618 octal power and energy measurement IC.