Specifications
Table Of Contents
- Coverpage
- Safety Instructions
- Revision History
- Contents
- Introduction
- 1 Outline
- 2 Explanation of Functions
- 3 Q-PLC Multi-CPU
- 4 Q Motion CPU
- 5 SFC Program
- 6 SV22 Servo Programs
- 6.1 Servo program
- 6.1.1 Servo program configuration
- 6.1.2 List of servo commands
- 6.1.3 Linear control
- 6.1.4 Circular interpolation control using auxiliary point designation
- 6.1.5 Circular interpolation control using radius designation
- 6.1.6 Circular interpolation control using center point designation
- 6.1.7 Fixed-dimension feed control
- 6.1.8 Speed control
- 6.1.9 Speed/position changeover control
- 6.1.10 Speed changeover control
- 6.1.11 Constant-speed control
- 6.1.12 Repeated control (for speed changeover control and uniform speed control)
- 6.1.13 Simultaneous start
- 6.1.14 Zero point return
- 6.1.15 Position follow-up control
- 6.1.16 High-speed oscillation control
- 6.1.17 Helical interpolation control with auxiliary point designated
- 6.1.18 Helical interpolation control with radius designated
- 6.1.19 Helical interpolation control with center point designated
- 6.1.20 Current value change
- 6.1 Servo program
- 7 Operation Control Program
- 8 Windows Personal Computer Operations
- 9 Basic Practice Using the SV22 Real Mode
- 10 Applied Practice with SV22 Real Mode
- 10.1 Details of practice
- 10.2 Q172CPU practice machine system configuration
- 10.3 Practice SFC programs
- 10.4 Writing to the motion CPU
- 10.5 Program for operation
- 10.5.1 JOG operation
- 10.5.2 Main routine SFC program (real mode operation)
- 10.5.3 Execution of servo program (motion control step)
- 10.5.4 Stopping
- 10.5.5 Error reset
- 10.5.6 Current value change
- 10.5.7 Speed change (CHGV)
- 10.5.8 Reading actual current value
- 10.5.9 Continuous positioning
- 10.5.10 M code function
- 10.5.11 Indirect setting of servo program address
- 10.6 Operating the practice machine
- 11 Practicing with the SV22 Virtual Mode
- 11.1 Mechanism program
- 11.2 Details of practice
- 11.3 Starting up SW3RN-CAMP and creating the cam
- 11.4 SFC program for virtual mode
- 11.5 Editing the mechanism
- 11.6 Writing to the motion CPU
- 11.7 Reading of sequence program from Q-PLC CPU
- 11.8 SFC program for practice
- 11.9 Practice machine operations
- 11.10 Exercise (Roller setting)
- Appendix

10 - 27
10.5.6 Current value change
Change the position at which the axis designated by CHGA command (change
address) of servo program is stopped to the set address.
CAUTION
Changing the current value during start may cause a minor error (code 300) to
occur, causing it to be unable to be executed.
(1) Current value change setting range
Current value change setting range
mm inch degree pulse
Setting
range
Unit
Setting
range
Unit
Setting
range
Unit
Setting
range
Unit
–2
31
to
2
31
–1
× 10
–4
mm
–2
31
to
2
31
–1
× 10
–5
inch
0 to
36999999
× 10
–5
deg
–2
31
to
2
31
–1
pulse
CAUTION
• Even if the set value is out of stroke range, it will not result in an error.
• –2
31
= –2147483648
• 2
31
–1 = +2147483647
(2) Program example
1) Current value change condition
Control axis Axis 1 Axis 2
Address after change 111.222mm
2) Example of SFC program to execute the servo program No.50 (to change
the current value of the stopped axis 1 forcibly to 111.222mm)
SFC program
No. 0
Real mode main
"Current value
change" is started
when X9 is turned
ON and M2001 is
turned OFF.
[Real mode main] program
Current value change
Current value change
SFC program No. 50
Servo program No. 50 start
K50: REAL
[Motion control step]
1 CHGA
AXIS 1, 111222.0µm
M2001 : Axis 1 start accept flag
PX09 : Current value change command
[Servo program]
Current value change command
Address after change of axis 1
(Set in 0.1µm units)
REAL
AXIS










