8. Mix another batch of concrete and add the black pigment. The ratio should be 1 ½ Lbs of pigment per 80Lbs of
concrete.
9. Pour the black concrete base from the bottom of the Sonotube form (10” below grade) to the top of the
Sonotube (28” above grade) vibrating frequently to relieve air bubbles.
Important: Hold the conduit and reinforcement in position as the concrete is poured and vibrated.
10. Position the tapered form so that the bottom is flush with the top of the Sonotube and so that the top of the
tapered form is at 29” above finished grade (1” above the top of the Sonotube). Level and set in place.
11. Pour the remaining black concrete to the top of the tapered form, vibrating frequently to evenly disperse the
concrete in the corners and relieve air bubbles.
12. Position (4) ½”x6” J-Bolts in the (4) perimeter
holes of the 8”x8”x1/16” steel mounting plate.
Use (8) ½” hex nuts to tighten the bolts in the
from the bottom. Install the (4) flat
washers, (4) locking washers and (4) ½” hex nuts
on the top side of the plate.
Important: The threaded portion of the J-bolts should not rise more than 1 ¼” above the top of the
steel mounting plate. Do not modify the steel
mounting plate for any reason.
13. Install the steel plate and J-Bolt assembly in the tapered
form and level. The top of the plate should be flush with
the top of the tapered form at 29” above grade.
14. Allow concrete to cure for 2-3 days.
15. Remove the Sonotube form, 12”x12” square tapered form
and backfill around the base. Allow concrete to cure for an
additional 2-3 days.
16. Cut the conduits so that they both rise 7/8”-1” above the top of the steel mounting plate.
17. Pass (6) 208/240V wires through the 1 ¼” conduit. Run the CAT5e Ethernet wire through the ¾” conduit and
install RJ45 connector. For installations using a cellular or Wi-Fi connection, the 12V power supply wire needs to
be included in the ¾” conduit from the station to router.
Important: Ethernet cabling should be CAT5e cable with a maximum segment length of 100 meters.
The Ethernet cable shall be gel-filled or rated for outdoor applications.
Figure 12
12”x12” Square
tapered form
(4) ½” Hex nuts
below and (4) above
Bottom side of
8”x8”x ¼” Steel
mounting plate
Figure 13
(4) ½”x6” J-Bolts