Portable Drying/Conveying Systems Chapter 6: Troubleshooting 67 of 76
Alarm Message Cause Corrective Action Dryer Status
Check the sensitivity setting of
the level sensor.
DH NO CONVEY
The level sensor on
the Drying hopper
material loader is not
detecting any
material.
Check the sensor, and replace
if necessary.
- Dryer Normal :
- Process blower ON.
- Process heaters ON.
- Regen heaters ON.
- Alarm Message ON.
- Alarm horn is OFF.
6-2 Determining Temperature Controller Errors or Sensor Errors
Using a Thermocouple
If the controller displays a temperature that is close to room temperature (70ºF/21ºC) when
you short-circuit controller input terminals, the controller is normal and the sensor is probably
broken, short-circuited, or incorrectly wired.
Other service problems or questions can be answered by contacting the Service
Department.