Alarm message Description Notes
Timing U Timing protection U
Configuration Parameters inconsistency
Configuration Relay key plug data inconsistency
Timing UV Timing protection UV
Timing OV Timing protection OV
Timing RV Timing protection RV
Timing RP Timing protection RP
Timing UF Timing protection UF
Timing OF Timing protection OF
13.6.4. Error messages displayed in pop-up windows
All the messages that appear on the display in a pop-up window are described below.
Error message Description
Password error
Session impossible
A programming session cannot be started due to a contingency (e.g. a timer-controlled
delay still elapsing)
Value outside range Value beyond the established limits
Exception 6 Control momentarily unavailable
Unavailable Function momentarily unavailable
Invalid date Date and time not updated. Set them.
Parameters revised Programming session concluded correctly
Cancelled Programming session cancelled
Failed Programming session rejected
Failed 1001 Inconsistent protection thresholds(L and S). Set: : I
1
<I
2
<I
3
Failed 1002 Inconsistent protection thresholds (S and I). Set: I
1
<I
2
<I
3
Failed 1009 SdZ incompatible SdZ directional
Failed 3001 Problems with language change
Failed 3002 Problems with toroid RC setting
Failed 3003 Problems with neutral setting
13.7. Troubleshooting PR122/P unit
The following table lists a series of typical service conditions, to help you understand and solve hypothetical faults or malfunctions.
Note:
1. Before consulting the following table, check for any error messages appearing for some seconds on the display.
2. FN indicates the normal operation of the PR122/P.
3. In the case where the suggestions proposed do not lead to a solution of the problem, please contact the ABB SACE assistance
service
Situation Possible causes Suggestions
1 The trip test cannot be run 1. The busbar current is > 0.
2. The TC is not connected
3. CB open
1. FN
2. Check the messages on the display
2 Trip times lower than expected 1. Threshold too low
2. Curve too low
3. Thermal memory enabled
4. Incorrect Neutral Selection
5. The SdZ is inserted
1. Correct threshold
2. Correct curve
3. Exclude if not necessary
4. Correct neutral selection
5. Exclude if not necessary
3 Trip times higher than expected 1. Threshold too high
2. Curve too high
3. Curve I
2
t inserted
4. Incorrect Neutral Selection
1. Correct threshold
2. Correct curve
3. Exclude if not necessary
4. Correct neutral selection
4 Rapid trip, with I3=Off Iinst tripped FN with short-circuit with high I
5 High earth I, but no trip happens 1. Incorrect selection of the sensor
2. Function G prevented with I>4In
1. Set int. or ext. sensor
2. FN
6 Display off 1. Vaux missing and the current and/or
voltages are below the minimum value.
2. Temperature out of range
1. FN, see 13.2.2.1
2. FN, see 13.2.9.8
7 The display is not back-lit Current and/or volatges below the limit for
lighting the display
FN