Specifications
L2234
L2778
L4681
L5179
Emax
69/161
Doc. No
Model
Apparatus
Scale
Page No
1SDH000460R0002
L5439
Select the menu item DATE to change
press the key (enter)
1/4
January 12, 2003
Time
Language
Date
System
You will be prompted to input a Password
complete the password entry procedure (par.13.3.6)
press the key (enter)
Password
Enter password
0***
Change the date using the key (arrow down)
(arrow up) and confirm by pressing the key (enter).
Press ESC twice to return to the Main Menu.
Date
Enter password
January 12, 2004
Procedure requiring the confirmation of any programming
For instance, to change the Curve of the Protection L, the correct sequence is as follows:
From the default page press ESC
to access the Main Menu
10:22:53
400A
(I )
1
U1 U2 U3 I1 I2 I3 In
From the Main Menu select the item PROTECTIONS
press the key (enter)
1/5
Protections settings
Measures
Settings
Protections
Menu
1/5
Protections settings
Measurements
Settings
Protections
Menu
From the Protections Menu select the item PROTECTION L
press the key (enter)
1/13
Overload
S Protection
I Protection
L Protection
Protections
From the Protection L Menu select the item CURVE
press the key (enter)
1/4
Threshold I1
Time T1
Function
L Protection
t=k/i
2
You will be prompted to input a Password (par. 13.3.6)
complete the password entry procedure
press the key (enter)
Password
Enter password
0***