1SDH000460R0002
L5439
13. SACE PR122/P Release - Identification
The PR122/P units available, in accordance with the IEC standards, together with the various protections and the various standard
and optional modules, are illustrated in the following figure:
Protections
For all versions
PR120/V - MEASURING
PR120/D-M - COM
PR120/K - SIGNALLING
PR120/D-BT - WL-COM
BT030 USB
Rc
(1)
Optional modules available
PR122/P
PR122/P
PR122/P
PR122/P
Note (1): See par. 16.5
13.1. Standard
The PR122/P has been designed to work in accordance with the international standard:
IEC 60947-2 Low voltage apparatus. Circuit-breakers.
13.2. Specifications
13.2.1. General
The PR122/P is a high-performance self-supplied protection unit with Protection, Measurement, Data storage, Communication
(optional), Self-test, Load control and Zone selectivity functions for the ABB SACE ‘Emax’ range of 3- and 4-pole low-voltage
air circuit-breakers. The unit’s user interface also enables parameter setup and complete the prealarm and alarm management
for the protection and watchdog functions.
The protections available are:
Symbol Protection against
L overload with inverse long time delay
S short-circuit with adjustable delay
I instantaneous short-circuit
G earth fault with adjustable delay
U phase unbalance
OT temperature out of range
MCR closing on short-circuit
The PR122/P can be installed on 3-pole CBs with and without an external neutral, or on 4-pole CBs.
It should be noted that the reference current for the PR122/P is the In (the rated current defined by the front Rating Plug) and not
the Iu (the uninterrupted rated current of the CB itself). Example: the CB E1B800 with a 400 A Rating Plug has an Iu of 800 A and
an In of 400 A.
The unit opens the circuit-breaker in which it is installed by means of the TC, which takes effect directly on the device’s mechani-
cal leverism.
The protection unit is self-supplied by current sensors and primary voltages if the PR120/V module is installed.