Installation and service instructions 1SDH000460R0002 L5439 Installation, service and maintenance instructions for low voltage air circuit-breakers Emax
Dwg. Resp. Off. L2234 L2778 L4681 L5179 Language Installation, service and maintenance instructions for low voltage air circuit-breakers Take over Off. App. Model Title L5439 ABB SACE Apparatus Doc. no.
Index 1. 1.1. 1.2. 1.3. 1.3.1. 1.3.2. 1.4. 1.5. Description . . . . . . . . . . . . . . . General characteristics . . . . . . . . . External front view of the circuit-breaker Rating plate . . . . . . . . . . . . . . . Circuit-breaker rating plate . . . . . . . Disconnector rating plate . . . . . . . . Moving part construction characteristics Fixed part construction characteristics . 2. Checking on receipt . . . . . . . . . . . . . . . . . . . 9 3. Storage, lifting and weights . . . . . . . . . . . . .
13.2.2.3. 13.2.3. 13.2.4. 13.2.4.1. 13.2.4.2. 13.2.5. 13.2.6. 13.2.6.1. 13.2.6.2. 13.2.6.3. 13.2.6.4. 13.2.7. 13.2.8. 13.2.9. 13.2.9.1. 13.2.9.1.1 13.2.9.2. 13.2.9.2.1 13.2.9.2.2 13.2.9.2.3 13.2.9.3. 13.2.9.3.1 13.2.9.4. 13.2.9.5. 13.2.9.5.1 13.2.9.5.2 13.2.9.6. 13.2.9.7. 13.2.9.8. 13.2.9.9. 13.2.9.9.1 13.2.9.9.2 13.2.9.9.3 13.2.9.9.4 13.2.9.10. 13.2.9.11. 13.2.9.12. 13.2.9.12.1 13.2.9.12.2 13.2.10. 13.2.10.1. 13.2.10.2. 13.2.10.3. 13.2.10.4. 13.2.10.5. 13.2.10.6. 13.2.10.7. 13.2.10.8. 13.2.10.9. 13.2.10.
14.2.9.10. 14.2.9.11. 14.2.9.11.1 14.2.9.11.2 14.2.9.11.3 14.2.9.11.4 14.2.9.12. 14.2.9.13. 14.2.9.14. 14.2.9.15. 14.2.9.16. 14.2.10. 14.2.10.1. 14.2.10.2. 14.2.10.3. 14.2.10.4. 14.2.10.5. 14.2.10.6. 14.2.10.7. 14.2.10.8. 14.2.10.9. 14.2.10.10. 14.2.10.11. 14.2.10.12. 14.3. 14.3.1. 14.3.1.1. 14.3.2. 14.3.3. 14.3.4. 14.3.5. 14.3.6. 14.3.7. 14.3.7.1. 14.3.7.2. 14.4. 14.4.1. 14.4.2. 14.4.3. 14.4.3.1. 14.4.4. 14.5. 14.5.1. 14.5.2. 14.5.2.1. 14.5.3. 14.5.3.1. 14.5.4. 14.5.4.1. 14.5.4.2. 14.5.4.2.1 14.5.4.3. 14.
16.4.4. 16.5. 16.5.1. 16.5.2. 16.5.3. 16.6. by the Data Logger system . . . . . . . . . . . . . . 134 Combination of devices for reading/setting data from the Data Logger system . . . . . . . . . . . . . 134 Access to saved data from the system . . . . . . . . 134 Information from the system on the configuration and status of the Data Logger . . . . . . . . . . . . . 135 Data logger commands from the system . . . . . . . 135 Table showing list of events . . . . . . . . . . . . . .
1. Description 1.1. General characteristics The SACE Emax series of circuit-breakers and disconnectors consists of a steel sheet structure which houses the operating mechanism, the poles and the auxiliary parts. Each pole, insulated from the others, contains the circuit-breaking parts and the current transformer of the corresponding phase. The structure of the poles differs according to whether the circuit-breaker is selective or current-limiting.
1.4.
2. Checking on receipt Examine the state of the material received and its consistency with the content of the order. Should any damage or errors be found on unpacking, which must be carried out carefully, make the relative notification within and not over 5 days from the receipt of the material. The notification must indicate the number of the shipping note. 3.
4. Installation 4.1. Installation room Install the circuit-breaker in a dry, dust-free, non-corrosive room, and in such a way that it is not subject to shocks or vibrations. Where this is not possible, install it inside a switchboard with a suitable degree of protection.
4.3.2. Installation of the fixed part (Fig. 12) Attach the fixed part by means of the screws (1), washers (2) and nuts (3) (M8 x 16), supplied by ABB SACE. if other screws are used, make sure that the head of the screws does not extend more than 5.5 mm from the base of the fixed part. 4.3.3. Installation of the fixed part on board a ship (Fig.
5. Electrical connections 5.1. Connections to the power circuit 5.1.1. Shapes of the terminals Fixed circuit-breaker Fixed part for withdrawable circuit-breaker HR HR VR Horizontal rear terminals Vertical rear terminals VR Horizontal rear terminals F Vertical rear terminals F Front terminals FL Front terminals Fig. 14 Flat terminals Fig. 15 Note The drawings are provided to show the type of terminal in graphic form.
Vertical terminals Circuit-breaker Iu [A] E3S/H/V 20 E3N/S/H/V 25 E3N/S/H/V 32 E3L 20 E3L 25 E4H/V 32 E4S/H/V 40 E6V 32 E6H/V 40 E6H/V 50 E6H/V 63 2000 2500 3200 2000 2500 3200 4000 3200 4000 5000 6300 Horizontal and front terminalsi Continuous currentcarrying capacity Busbar crosssection Continuous currentcarrying capacity Busbar crosssection [A] [mm2] [A] [mm2] 35°C 45°C 55°C 2000 2500 3200 2000 2500 3200 4000 3200 4000 5000 6000 2000 2500 3100 2000 2390 3200 3980 3200 4000 4850 5700 200
5.1.3. Assembly procedure for the connection busbars Check the state of the contact surfaces of the connections very carefully: they must be very clean with no burrs, dents or traces of rust which must be eliminated using a fine file or an emery cloth to prevent localized increases in temperature. On completion of the operation, remove all traces of grease or dust with a cloth soaked in a suitable solvent. When alluminium connections the contact surfaces must be tinned.
5.3.2. Withdrawable circuit-breaker For connection of the moving part to the auxiliary circuits, a connection with sliding contacts is available on the fixed part (see figure), identified by code X on the electrical circuit diagram. The terminals of the fixed connector are immediately accessible when the compartment door is open. Furthermore a terminal box identified by code XF is available for connecting the position contacts of the moving part in relation to the fixed part.
5.4. Conversion of the auxiliary contacts or of the signalling contacts (disconnected - test isolated - connected), from normally closed (opening) to normally open (closing) or vice versa The contacts are wired at the factory as shown on the electrical circuit diagram. If it is necessary to change their state for installation requirements, proceed as follows.
6. Putting into service 6.1. General procedures - Check tightness of the power connections at the circuit-breaker terminals - Carry out all the preparatory operations on the release - Make sure that the value of the auxiliary circuit power supply voltage is between 85 and 110% of the rated voltage of the electrical applications - Make sure that there is an adequate air circulation in the place of installation to avoid overheating - Also carry out the checks specified in the following table.
7. Instructions for use 7.1.
7.2. Circuit-breaker closing and opening procedures The operation of the circuit-breaker can be either manual or electrical.
7.3. Racking-in/out operation WARNING A) Open the circuit-breaker before carrying out any racking-in/out operation. B) The circuit-breaker (moving part) and fixed part are fitted with a lock which prevents the fixed part from being racked into the circuit-breakers with a different rated current: the congruence of the anti-racking-in lock must be checked by the operator before carrying out the racking-in operation to avoid any unnecessary stress.
a) Positioning the moving part in the fixed part in the DISCONNECTED position Lift the moving part as shown in the paragraph (3) and insert it in the fixed part guide, tilting it as shown in figure 2. The manual connection must allow the edge (E) of the circuit-breaker guide to slide under the blocks (D) of the fixed part. Remove the lifting devices. The position reached is stable and allows for any inspections of the circuit-breaker. Push the moving part as far as the stop in the fixed part.
8. Maintenance 8.1.
8.2.2. Maintenance program The table shows the maintenance intervals and the frequency of periodical intervention and routine maintenance tasks. The following rules should also be followed: - Even circuit-breakers that are little used or remain on or off for long periods should be subject to the maintenance programme.
8.3.4. Dismantling tab and cap - The tab (1) of the release by rotating the screws (2) as shown in figure 33. - Remove the front cap (3) by loosening the four screws (4). 2 2 1 1 3 4 4 3 Fig. 33 - If there is a minimum release, remove the coils support and release the control springs, closing and opening the switch. Fig. 34 8.3.5. Mechanical control - Clean at the points indicated in figure 35. For excessive deposits, a laminated dilutant such as Henkel 273471 or the equivalent can be used.
8.3.6. Electrical and mechanical accessories - Check that the accessories are fixed to the switch - Check that the electrical accessories are connected to the switch - Reduction gear: after 10000 operations check brushes for wear and replace the reduction gear if necessary. - Check that the releases (SOR-UVR-SRC) are in good condition (no excessive wear, overheating, breakages) Fig. 36.
8.4. Second level maintenance operations 8.4.1. Preliminary operations: - open the switch and check that the control springs are unloaded - in the case of a circuit breaker, remove the circuit breaker from the fixed part before working on it WARNING: before working on fixed switches or switches on fixed parts, disconnect the supply to the power circuit and to the auxiliary circuits and earth the terminals in a visible manner both on the supply and on the load side. 8.4.2.
8.4.4. Dismantling the tab, cap and arcing chambers - Remove the flange (1) of the release, turning the screws (2) as shown in the figures - Remove the front escutcheon plate (3) by removing the four screws (4) - Remove, if present, one or both side guards (5) by removing the front (6) and lateral (7) screws - Remove the arcing chambers (8) by removing the screws (9). Fig. 41 - If there is a minimum release, dismantle the coil support and unload the control springs by opening and closing the switch. Fig.
8.4.5. Mechanical control - Cleaning (for excessive deposits, a laminated dilutant such as Henkel 273471 or the equivalent can be used) and lubricate, at the points indicated in fig. 43, part A, as for First Level, the opening and closing shafts and hooks with MOBILGREASE 28 (EXXON MOBIL).
6.1) Check the blowout magnets distances (distance A fig 45). Circuit Breaker Fig. 45 6.2) close the circuit-breaker and check the gap A - If the gap A is not correct, contact ABB Sace (*) - If the gap A is correct, open the circuit breaker and refit the arc chambers. (*) Subject to the customer’s approval, ABB can replace “A” type parts. 8.4.8. Protection releases - Supply the protection release with a PR030/B battery unit.
- Return the movable part to the position TEST-ISOLATED.
9.
10. Accessories 10.1. Electrical accessories Shunt opening/closing (YO/YC) and second shunt opening release (Y02) This allows remote opening or closing control of the apparatus. Given the characteristics of the circuit-breaker operating mechanism, opening (with the circuit-breaker closed) is always possible, whereas closing is only possible when the closing springs are loaded. Most of the releases can operate with either direct or alternating current.
Reference figures in the electrical circuit diagrams: YU + D; (7). The characteristics of the time-delay device are: 24-30 V AC/DC 48 V AC/DC Power supply (D): 60 V AC/DC 110-127 V AC/DC 220-250 V AC/DC Adjustable opening time (YU+D): 0,5-1-1,5-2-3 s Geared motor for automatic closing spring loading (M) This automatically loads the circuit-breaker operating mechanism closing springs. After circuit-breaker closing, the geared motor immediately sees to reloading the closing springs.
The versions available are: a) Electrical signalling for circuit-breaker open/closed It is possible to have electrical signalling of the circuit-breaker status (open/closed) 4, 10 or 15 auxiliary contacts.
Transparent protection covers a) Protection covers for opening and closing pushbuttons These protection covers, applied over the opening and closing pushbuttons, prevent the corresponding circuit-breaker operations except by using a special tool. b) IP54 door protection This is provided by means of a transparent plastic escutcheon plate which fully protects the front of the circuit-breaker and ensures a degree of protection to IP54. Mounted on hinges, it is fitted with a key lock.
10.3.
11. Protection releases - General notes Emax, the range of ABB air circuit-breakers, now has a new range of electronic relays. These are called PR121, PR122 and PR123, and they substitute the previous range PR111, PR112 and PR113. The new protection releases integrate all the functions of their predecessors, adding new and interesting technical features that are useful for satisfying every current and future system installation need.
If in doubt, about its safe usage, the unit must be put out of service to prevent any accidental use. You must assume that safe usage is impossible if: 1. the unit shows visible signs of damage. 2. the unit does not function (for example with autotest or with the trip test unit). 3. the unit has been damaged in transit. WARNING: Prior to servicing and/or replacing, the circuit-breaker must be open. Also remember to disconnect all power supplies connected. 11.1.1.
12. SACE PR121/P Release - Identification The PR121/P units available, in accordance with the IEC Standards, with the various default and optional protections and modules, are illustrated in the figure below: PR121/P PR121/P PR121/P Protections Optional modules available BT030 USB PR030/B 12.1. Standard The PR121/P has been designed to work in accordance with the following international standard: IEC 60947-2 Low voltage apparatus. Circuit-breakers. 12.2. Specifications 12.2.1.
12.2.2.2. Auxiliary power supply The outside auxiliary power supply is provided using a galvanically-separated power pack. WARNING: Since the auxiliary voltage needs to be isolated from the ground, “galvanically separated converters” in accordance with the IEC standard 60950 (UL 1950) or the equivalent IEC 60364-41 and CEI 64-8 have to be used to guarantee a current in common mode or leakage current (as defined in IEC 478/1 and CEI 22/3) no greater than 3.5 mA.
12.2.6. Description of the protection functions 12.2.6.1. Protection “L” The “L” is the only protection that cannot be disabled because it is for self-protection against overloading of the relay itself. The type of curve that can be set is t=k/I2. The inverse-time protection trip time is given by the expression: Max 9 t1 2 (If / I1) ,1 where lf ≤ 12ln, 1 s where lf > 12ln If is the fault current and I1 the protection threshold, established by the user. NB: Time expressed in seconds. 12.2.6.1.
Protection Disabling I (t=k) G (t=k) Trip threshold Trip time Trip threshold tolerance (2) ≤ 30 ms ± 10% I3 = 1,5 - 2 - 3 - 4 - 5 - 6 - 7 - 8 - 9 10 - 11 - 12 - 13 - 14 - 15 x In I4 = 0,2 - 0,3 - 0,4 - 0,6 - 0,8 - 0,9 1 x In Where If > I4 t4 = 0.1 - 0.2 - 0.4 - 0.8 s ± 7% ± 10% o ± 40 ms G (t=k/I2) I4 = 0,2 - 0,3 - 0,4 - 0,6 - 0,8 - 0,9 1 x In ± 7% ± 15% I inst Automatic, defined by SACE Minimum trip time t4 = 0.1 - 0.2 - 0.4 - 0.
12.2.9.2. Trip curves for functions L-S(t =k/I2)-I t= k I2 12.2.9.3. Trip curves for functions L-S(t=k)-I t=k Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
12.2.9.4. Trip curves for function G t= k 2 I t=k 12.3. Other functions 12.3.1. Indication of the cause of the trip and trip test button Using the “i Test” button, you can retrieve the information stored in the past 48 hours. You can also perform a trip test by pressing and holding the button for 7 seconds and an Autotest by pressing and holding the button for 3 seconds, again with the PR030/B battery unit connected and no current flowing through. 12.4. Putting into service 12.4.1.
12.5. User interface Captions on the front of the PR121/P unit: 17 20 Ref.
12.5.3. Changing protection functions This paragraph enables the user to set the protection functions implemented in the PR121/P unit. Only the setting methods and which values can be selected are explained here. For all other information on the technical characteristics of the protection functions, see par. 12.2.5. WARNING: No parameter settings can be made if the PR121/P unit is in alarm conditions. 12.5.3.1. Example of settings In the diagrams on the front plate (see par. 12.
12.6.3. Replacing an electronic release To complete the procedure for installing PR121/P take the following steps: 1. With the circuit-breaker open and possibly disconnected, install the protection unit on the circuit-breaker. 2. Power the unit with the PR030/B ONLY. 3. If there are no errors other than the configuration error (see par. 12.7.1), press and hold the “i Test” button for a few seconds until all the red LEDs start to flash to confirm that installation is complete. 4. Remove the PR030/B. 5.
12.7.2. Troubleshooting The following table lists a series of typical service conditions, to help you understand and solve hypothetical faults or malfunctions. N.B.: 1. Before consulting the following table, check for a few seconds for any optical signals provided by the LEDs. 2. FN indicates the normal operation of the PR121/P. 3. If the following suggestions fail to solve the problem, please contact the ABB SACE customer support service.
13. SACE PR122/P Release - Identification The PR122/P units available, in accordance with the IEC standards, together with the various protections and the various standard and optional modules, are illustrated in the following figure: PR122/P Protections PR122/P PR122/P PR122/P For all versions Optional modules available PR120/V - MEASURING PR120/D-M - COM PR120/K - SIGNALLING PR120/D-BT - WL-COM BT030 USB Rc(1) Note (1): See par. 16.5 13.1.
The unit is made using digital microprocessor technology and interfaces with the user by means of a graphic display and keyboard. With the optional PR120/V module, the PR122/P also assures the following protections: Symbol UV OV RV RP UF OF U Protection against undervoltage overvoltage residual voltage reverse active power underfrequency overfrequency phase-to-phase voltage unbalance (as an alternative to phase currents) 13.2.2.
13.2.5. Communication bus Local bus on rear connector; RS485 physical interface, Modbus protocol. External system bus, RS485 physical interface, Modbus RTU protocol, baud rate 9600-19200 bps. Test bus on front test connector. 13.2.6. Protection functions The PR122/P protection unit carries out 8 independent protection functions. In particular: 1. Protection against overload with inverse time “L”; 2. Protection against short-circuit with adjustable delay “S”; 3.
13.2.8. Watchdog The PR122/P unit provides some watchdog functions able to guarantee the proper management of relay malfunctions. These functions are as follows: Watchdog for presence of Auxiliary power supply with “plug” icon displayed. RATING PLUG validity. Watchdog for proper connection of the current sensors (CS). If it is enabled, any anomalies are indicated by a special alarm message and the “alarm” LED coming on, and the circuit-breaker opens after 1s.
The function can be disabled and it is a setting characteristic of the single protection units. The start-up function enables the protection threshold (S, I and G) to be changed during a time interval lasting “ts”, starting from “start-up”. The latter must be intended as follows: - Passage of at least one of the phase currents above the activation threshold of the adjustable Start-Up with SD TestBus2, Ekip Connect or PR010/T (0.1…10In, by 0.
to guarantee correct operation of the relay on the supply side. 13.2.9.3.1 Start-up threshold “I” The start-up function can be selected. The function can be enabled from the menu on the protection “I” page. The function behaves in exactly the same way as the protection “S” (see par. 13.2.9.9.2). 13.2.9.4. Protection “MCR” against closing on short-circuit The MCR function is used to protect the system against closing.
% Unb = I max − I min . 100 where Imax is the maximum and Imin is the minimum phase current. I max WARNING: It is possible to disable the trip control of the protection (“Enable Trip: Off”). In that case, for the whole duration of the unbalance the CB will not be opened, but only the condition will be signaled by means of the “warning” LED lit up and a warning message.
This protection is available on 4-pole or 3-pole CBs with neutral voltage available (see circuit diagram 48). On 3-pole CBs, presence of neutral voltage must be set by the “neutral voltage present” parameter. 13.2.9.9.4 Protection “U” The disable-type, fixed-time protection trips when - for a time higher than or equal to t6 time set - an unbalance between two or more line voltages greater than I6, is detected. Range: 2 … 90%, by 1% Step. Max.
LC1/LC2 loads Controll Warning Iw (1) (2) (3) (4) (5) (6) Thermal memory Start-up threshold Zone selectivity Disabling of TRIP only Disabling Protection Trip Threshold Trip time Trip threshold tolerance (2) Trip time tolerance (2) ± 10% 10÷40 ms 50%100% step 1%xI 1 0,310In step 0,05xIn The minimum value of this trip is 1s regardless of the type of curve set (self-protection).
Standard operation Range Tollerance % Range of values measured by the relay Type of measurement range External ground fault current (external source round return) Phase-to-phase and phase voltages (measured at the module's input and thus independent of the precision relating to the use of any VT) Residual voltage (for systems with neutral only) Peak factor Total power factor Mains frequency Instantaneous active power on the ± 2,5 single phase and total system Instantaneous active power on the ± 2,5 single
13.2.10.2. Trip curves for functions L-S(t=k/I2)-I t [s] 10 4 L 0,4 ... 1 0,4 1 10 3 0,6 ... 10 0,6 10 S 3 ... 144 10 2 t= 1,5 ... 15 1,5 10 k 2 I 15 0,05 ... 0,8 I 1 10 -1 10 -2 10 -3 10 -1 1 10 100 x In 13.2.10.3. Trip curves for functions L-S(t=k)-I t [s] 10 4 0,4 … 1 L 0,4 1 10 3 0,6 … 10 0,6 10 3 … 144 S 10 2 t=k 1,5 … 15 1,5 15 10 I 1 10 -1 0,05 … 0,8 10 -2 10 -3 10 -1 Model L2234 L2778 1 L4681 L5179 L5439 10 Apparatus Doc.
13.2.10.4. Trip curves for function L in accordance with IEC 60255-3 (type A) t [s] 10 4 0,4 1 0,4 … 1 L 10 3 k=0,14 a=0,02 10 2 3 … 144 10 1 10 -1 10 -1 1 10 100 x In 13.2.10.5. Trip curves for function L in accordance with IEC 60255-3 (type B) t [s] 10 4 0,4 1 0,4 … 1 L 10 3 k=13,5 a=1 10 2 3 … 144 10 1 10 -1 Model L2234 L2778 10 -1 1 L4681 L5179 L5439 10 Apparatus Doc. no.
13.2.10.6. Trip curves for function L in accordance with IEC 60255-3 (type C) t [s] 10 4 0,4 1 0,4 … 1 L 10 3 k=80 a=2 10 2 3 … 144 10 1 10 -1 10 -1 1 10 100 x In 13.2.10.7. Trip curves for function G t [s] 10 4 0,2 … 1 1 0,2 10 3 10 2 t= 10 k I2 G 1 0,1 10 …1 10 -1 G t=k 10 -2 10 -3 10 -1 Model L2234 L2778 1 L4681 L5179 L5439 10 Apparatus Doc.
13.2.10.8. Trip curves for function U t [s] 10 4 0,02 … 0,9 0,9 0,02 U 10 3 10 2 60 10 1060 0,5 … 1 0,5 10 -1 10 -2 10 -1 1 10 x In 13.2.10.9. Trip curves for function UV t [s] 10 4 0,5 … 0,95 0,5 0,95 UV 10 3 10 2 10 5 1 105 0,1 … 10 -1 0,1 10 -2 0,3 Model L2234 L2778 0,5 L4681 L5179 0,7 L5439 0,9 Apparatus Doc. no.
13.2.10.10. Trip curves for function OV t [s] 10 4 1,05 … 1,2 1,05 1,2 OV 10 3 10 2 10 5 1 105 0,1 … 10 -1 0,1 10 -2 1 1,05 1,1 1,15 1,2 1,25 1,3 x Un 13.2.10.11. Trip curves for function RV t [s] 10 4 0,1 … 0,4 0,1 0,4 RV 10 3 10 2 30 10 0,5 …10 30 1 0,5 10 -1 0 0,2 0,4 0,6 0,8 1 1,2 x Un Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
13.2.10.12. Trip curves for function RP 13.3. Putting into service 13.3.1. Connections WARNING: For the connections provided by the user, it is recommended that you comply strictly with the recommendations contained in this document. This will enable us to satisfy all the international reference standards and guarantee perfect operation of the relay even under severe environmental and electromagnetic conditions.
13.3.2. VT connections WARNING: Dielectric strength tests are not allowed on the inputs and outputs of the releases or on the secondary lines of any connected VTs. The following is a summary table of standard VT connections according to the type of plant. VT Standard (A): Single standard transformers, see par. 15.1.7. The VTs must have a performance coming between the values of 10 and 20 VA inclusive, 4 kV insulation between the primary and secondary.
13.3.6. Password management Specify a password? [0***] To enter “EDIT” mode it is necessary to enter a four-figure numerical password. The values attributable to the password go from 0000 to 9999. For the default password see par.13.4.4. Select the value of the first figure ( between ‘0’ and ‘9’ ) by means of the and and press to confirm the figure and then move on to enter the next one. After entering the fourth figure, check the password you have entered.
13.4. User interface 1 2 3 7 6 Ref.
13.4.2. Read and Edit modes The menus map (see par. 13.5.1) shows all the pages which can be obtained and how to move between them from the keyboard, in the “READ” mode (just to read the data) or in the “EDIT” mode (to set the parameters). Starting from any page displayed, after about 120 sec of inactivity, the default page will be automatically displayed (see par. 13.5.1).
1/4 System Select the menu item DATE to change Date Time Language press the key (enter) January 12, 2003 Password You will be prompted to input a Password complete the password entry procedure (par.13.3.6) 0*** press the key (enter) Enter password Change the date using the key (arrow down) Date (arrow up) and confirm by pressing the key (enter). January 12, 2004 Enter password Press ESC twice to return to the Main Menu.
Select the value you want from the list and confirm pressing the key (enter). 1/4 Function t=k/i2 0.02 t=0.14b/(i -1) T=13.5b/(i-1) Press ESC twice Before accessing the Main Menu, the following box will appear: 1/3 Programming Accept the new configuration Confirm Abort Reject the new configuration (the previous configuration is retained) Modify Change the previously input values. Confirm To select the required option use the (arrow down), (arrow up) keys, and press (enter) to confim.
13.4.4. Default settings The PR122/P is supplied by ABB SACE with the following predefined parameters: # 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Protection L S I G U (currents) OT K LC1 K LC2 UV OV RV RP UF OF Language Net frequency PR021/K Neutral sel. Toroid sel. Ext. ground tor.
13.5. Operating instructions / Operation in service 13.5.1. Menu As seen previously, the PR122/P uses the display to show messages, diagrams and menus. These are organized in a logical and intuitive way.
Each time the unit is turned on, or after more than 2 minutes of inactivity on the keyboard, the display indicates the following. page (default): Percentage of the actual currents and voltages with respect to the rated values (100%) 10:22:53 Current of the phase under the greatest load 400A (I1) Indication for the phase under the greatest load (L1, L2, L3, N) U1 U2 U3 I1 I2 I3 In 13.5.2.
Protection Gext Parameter / Function Enable Curve Threshold I4 Time t4 Enable Trip Zone selectivity Selectivity time Enable StartUp StartUp threshold StartUp time Threshold I4 Time t4 Enable Function Threshold I6 Time t6 Enable Trip Enable Threshold U8 Time t8 Enable Trip Enable Threshold U9 Time t9 Enable Trip Enable Threshold U10 Time t10 Enable Trip Enable Threshold P11 Time t11 Enable Trip Enable Threshold f12 Time t12 Enable Trip Enable Threshold f13 Time t13 Enable Trip Enable Trip Threshold 1 Enable
13.5.3.1. Measurements Menu table Protection Historicals Parameter / Function Trips Events Measurements I Max Reset measurements Values Notes Last trip (20) Events log (80 events max.) Current Peak factor Contact wear Percentage of wear on CB contacts 13.5.4. Settings Menu 1/5 Menu Protections Measurements Settings The configuration parameters in the Settings menu are password protected.
13.5.4.2. Neutral adjustment The neutral protection is normally set to a current value 50% of the adjustment made on the phases. In some installations, where particularly high harmonics occur, the current circulating on the neutral may be higher than that of the phases. In the SACE PR122/P release, this protection can be set for the following values: InN= 50% - 100% - 150% - 200% * In. 13.5.4.2.1 Neutral adjustment specifications Neutral (InN) adjustment must meet the following formula: I1 x InNIu.
13.5.5. Test Menu Access to the Test menu is password protected. 4/5 Menu Measures Password Enter Settings 1/6 Test Enter 0*** Test CB status Auto Test Trip Test (disabled) Enter password Device test CB open The menu shows the state of the CB, in the dialog module (COM module) the state of the springs and the position of the CB, and in this submenu you can make the CB open or close. Using the “Trip Test” function lets you view the disabling/enabling of the Trip.
Access to view the opening data is via the Historicals submenu in the Measurements menu. The following is an example of the information provided: N.02 1/3 Last Trip Number of openings due to the protections. 15 Feb 2004 L Protection I1: 625A I2: 617A I3: 623A N: > 10.0 kA Indication for protection tripped. Value of the currents interrupted on phases (L1, L2, L3), neutral (Ne) and Ground (if G has been tripped).
13.6.3. Table of error and warning messages All the messages which can be shown on the display relating to incorrect configurations, generic alarms or deriving from the protection functions and linked to useful information are described below. The following symbols in the warning signals have the following meanings: = Warning signal / Protection in alarm mode, with no trip (trip=off). =Protection in alarm mode, with trip at end of delay (trip=on) =Information, no action, excepting displaying by the relay.
Alarm message Description Notes Timing U Timing protection U Configuration Parameters inconsistency Configuration Relay key plug data inconsistency Timing UV Timing protection UV Timing OV Timing protection OV Timing RV Timing protection RV Timing RP Timing protection RP Timing UF Timing protection UF Timing OF Timing protection OF 13.6.4. Error messages displayed in pop-up windows All the messages that appear on the display in a pop-up window are described below.
N° Situation 8 Reading of V, W and power factor 9 Reading of V, W and power factor incorrect 10 “ Local Bus” message on display 11 Message " " instead of expected data 12 The expected trip does not occur 13 No activation of the Unbalance U protection 14 No display of the opening data 15 The password is not requested 16 Impossible to change any parameter 17 “ Temp.
14. SACE PR123/P Release - Identification The PR123/P units available, in accordance with the IEC standards, together with the various protections and the various standard and optional modules, are illustrated in the following figure: PR123/P PR123/P Protections For all versions 2 Optional modules available PR120/D-M - COM PR120/K - SIGNALLING PR120/D-BT - WL-COM BT030 USB Rc(1) Note (1): see par. 16.5 14.1.
14.2.2. Electrical characteristics Rated operating frequency Pass band Peak factor 50/60 Hz ±10% 2500 Hz max 2,1 @ 2xIn in conformity to IEC 9472 Annex F. For greater peak factors,consult ABB 14.2.2.1. Self-powering Self-powering enables the protection unit to be powered with the busbar current using current transformers. Using this supply mode, only the unit’s protection functions are assured, however, not the accessory functions regarding the modules.
8. 9. 10. 11. 12. 13. 14. 15. Protection against phase unbalance “U”; Protection against overtemperature “OT”; Protection against undervoltage “UV”; Protection against overvoltage “OV”; Protection against residual voltage “RV”; Protection against reverse active power “RP”; Underfrequency “UF”; Overfrequency “OF”. The PR123/P unit allows current signal processing of the neutral pole with different relationships relative to the value of the phases. N.B.: Beyond 15.
14.2.8. Watchdog The PR123/P unit provides some watchdog functions able to guarantee the proper management of relay malfunctions. These functions are as follows: Watchdog for presence of Auxiliary power supply with “plug” icon displayed. RATING PLUG validity. Watchdog for proper connection of the current sensors (CS). If it is enabled, any anomalies are indicated by a special alarm message and the “alarm” LED coming on, and the circuit-breaker opens after 1s.
14.2.9.2.2 Start-up threshold “S” The start-up function can be selected in the case where the curve with fixed time is selected. The start-up function can be selected in the case where the curve with fixed time is selected. The function can be disabled and it is a setting characteristic of the single protection units. The start-up function enables the protection threshold (S, D, I and G) to be changed during a time interval lasting “ts”, starting from “start-up”.
14.2.9.3. Double S Thanks to the new PR123/P release that enables two independent and simultaneously active protection S thresholds to be specified, selectivity can assured even in critical conditions. This function enables a better selectivity level to be obtained than using a release without a “double S”. This function is valid for t=K only. 14.2.9.4.
The general behavior is summarized in the table below. (Example with power flow setting “Top Bottom”). Ifault (If) Value If < I7 If > I7 If > I7 If > I7 If > I7 Outputs status Direction either Top Bottom Top Bottom Bottom Top Bottom Top DFout 0 1 1 0 0 Inputs status DBout 0 0 0 1 1 DFin either 0 1 either either T trip DBin either either either 1 0 No trip ts t7FW t7BW ts If the power flow is in phase with the direction set on the relay, the output DFout is enabled (1).
14.2.9.5.1 Start-up threshold “I” The start-up function can be selected. The function can be enabled from the menu on the protection “I” page. The function behaves in exactly the same way as the protection “S” (see par. 14.2.9.2.2). 14.2.9.6. Protection against closing on short-circuit “MCR” The MCR function is used to protect the system against closing. If activated (the protection can be enabled/disabled), it operates only in the presence of Vaux or PR120/V, and with Protection “I” disabled.
14.2.9.9. Protection against overtemperature inside the relay “OT” There is a sensor inside the PR123/P unit that monitors the temperature of the unit. This enables the signalling of any abnormal temperature conditions, which could cause temporary or continuous malfunctions of the unit’s electronic components. This protection has two states of operation: State of “WARNING TEMPERATURE” with –25°C < temp. < -20°C or 70°C < temp. < 85°C : the display is turned off and the “WARNING” LED flashes at 0.
14.2.9.12. Protection against reverse active power “RP” The PR123/P unit provides protection (which can be disabled) with an adjustable fixed time (t = k), against reverse active power, active both with self-powering and auxiliary supply. When the total reverse active power (sum of the power of the 3 phases) exceeds the set reverse active power threshold P11 the protection counts down the preset time interval t11 and then opens.
U (t=k) Thermal memory Start-up threshold Zone selectivity Disabling TRIP only Disabling Protection Threshold range Time range 2% I6 90% step 1% Time Tolerance (2) 0,5 s t6 60 s, step 0,5 s ± 10% The best of the two data Instantaneous ± 5°C OT (temp=k) Iinst UV (t=k) OV (t=k) RV (t=k) 0,1xUn ≤ U ≤ 0,4xUn 0,5 s t 30 s, step 0,5 s step 0,05 Un10 10 ± 5% RP (t=k) - 0,3xPn ≤ P11 ≤ -0,1xPn step 0,02 Pn
14.2.9.16.
14.2.10.2. Trip curves for functions L-S(t=k)-I t [s] 10 4 0,4 ... 1 L 0,4 1 10 3 0,6 ... 10 0,6 10 3 ... 144 10 2 S t=k 1,5 ... 15 1,5 15 10 I 1 10 -1 0,05 ... 0,8 10 -2 10 -3 10 -1 10 1 100 x In 14.2.10.3. Trip curves for function G 0,2 ... 1 0,1 ... 1 Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc. no.
14.2.10.4. Trip curves for function L in accordance with IEC 60255-3 (type A) t [s] 10 4 0,4 1 0,4 … 1 L 10 3 k=0,14 α=0,02 10 2 3 … 144 10 1 10 -1 10 -1 10 1 100 x In 14.2.10.5. Trip curves for function L in accordance with IEC 60255-3 (type B) t [s] 10 4 0,4 1 0,4 … 1 L 10 3 k=13,5 α=1 10 2 3 … 144 10 1 10 -1 Model L2234 L2778 10 -1 1 L4681 L5179 L5439 10 Apparatus Doc.
14.2.10.6. Trip curves for function L in accordance with IEC 60255-3 (type C) t [s] 10 4 0,4 1 0,4 … 1 L 10 3 k=80 α=2 10 2 3 … 144 10 1 10 -1 10 -1 1 10 100 x In 14.2.10.7. Trip curves for function D t [s] 10 4 10 3 0,6 ... 10 0,6 10 D 10 2 10 1 0,2 ...10 0,8 10 -1 Model L2234 L2778 10 -2 10 -1 L4681 L5179 1 L5439 10 Apparatus Doc. no.
14.2.10.8. Trip curves for function U t [s] 10 4 0,02 … 0,9 0,9 0,02 U 10 3 10 2 60 10 1060 0,5 … 1 0,5 10 -1 10 -2 10 -1 1 10 x In 14.2.10.9. Trip curves for function UV t [s] 10 4 0,5 … 0,95 0,5 0,95 UV 10 3 10 2 10 5 1 105 0,1 … 10 -1 0,1 10 -2 0,3 Model L2234 L2778 0,5 L4681 L5179 0,7 L5439 0,9 Apparatus Doc.
14.2.10.10. Trip curves for function OV t [s] 10 4 1,05 … 1,2 1,05 1,2 OV 10 3 10 2 10 5 1 105 0,1 … 10 -1 0,1 10 -2 1 1,05 1,1 1,15 1,2 1,25 1,3 x Un 14.2.10.11. Trip curves for function RV t [s] 10 4 0,1 … 0,4 0,1 0,4 RV 10 3 10 2 30 10 0,5 …1030 1 0,5 10 -1 Model L2234 L2778 0 0,2 L4681 L5179 0,4 L5439 0,6 0,8 Apparatus Doc. no.
14.2.10.12. Trip curves for function RP t [s] 10 4 -0,3 … -0,1 -0,3 -0,1 RP 10 3 10 2 25 10 0,5 …1025 1 0,5 10 -1 -0,4 -0,3 -0,2 0 x Pn -0,1 14.3. Putting into service 14.3.1. Connections WARNING: For the connections provided by the user, it is recommended that you comply strictly with the recommendations contained in this document.
14.3.2. VT connections WARNING: Dielectric strength tests are not allowed on the inputs and outputs of the releases or on the secondary lines of any connected VTs. The following is a summary table of standard VT connections according to the type of plant. VT Standard: Single standard transformers, see par. 15.1.7. The VTs must have a performance coming between the values of 10 and 20VA inclusive, 4 kV insulation between the primary and secondary.
14.3.6. Password management Specify a password? [0***] To enter “EDIT” mode it is necessary to enter a four-figure numerical password. The values attributable to the password go from 0000 to 9999. For the default password see par. 14.4.4. Select the value of the first figure ( between ‘0’ and ‘9’ ) by means of the and keys and press to confirm the figure and then move on to enter the next one. After entering the fourth figure, check the password you have entered.
14.4. User interface 1 2 3 4 5 8 Rif.
14.4.2. Read and Edit modes The menus map (see par. 14.5.1) shows all the pages which can be obtained and how to move between them from the keyboard, in the “READ” mode (just to read the data) or in the “EDIT” mode (to set the parameters). Starting from any page displayed, the default page will be automatically displayed after about 120 sec inactivity (see par. 14.5.1).
1/4 System Select the menu item DATE to change Date Time Language press the key (enter) January 12, 2003 Password You will be prompted to input a Password complete the password entry procedure (par. 14.3.6) 0*** press the key (enter) Enter password Date Change the date using the keys (arrow down) (arrow up) and confirm by pressing the key (enter). January 12, 2004 Enter password Press ESC twice to return to the Main Menu.
Before accessing the Main Menu, the following box will appear: 1/3 Programming Accept the new configuration Confirm Abort Reject the new configuration (the previous configuration is retained) Modify Change the previously input values. Confirm To select the required option use the (arrow down), (arrow up) keys, and press (enter) to confirm. 14.4.3.1. Modification of basic configuration No parameter settings can be made if the PR123/P unit is in alarm conditions.
14.4.4. Default settings The PR123/P is supplied by ABB SACE with the following predefined parameters (Set A and Set B): # 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 Protection L S D I G U OT K LC1 K LC2 UV OV RV RP UF OF Language Net Frequency PR021/K Neutral sel. Toroid Selec. Ext. ground tor.
14.5. Operating instructions / Operation in service 14.5.1. Menu As seen previously, the PR123/P uses the display to show messages, diagrams and menus. These are organized in a logical and intuitive way. The following is a general layout showing how to access the main menu pages.
Each time the unit is turned on, or after more than 2 minutes of inactivity on the keyboard, the display indicates the following page (default): Percentage of the actual currents and voltages with respect to the rated values (100%) 10:22:53 Current of the phase under the greatest load 400A (I1) Indication for the phase under the greatest load (L1, L2, L3, N) U1 U2 U3 I1 I2 I3 In 14.5.2.
Protection S2 Parameter / Function Enable Threshold I2 Time t2 Zone selectivity Selectivity time Enable StartUp StartUp threshold StartUp time Enable Threshold I7 Time t7 Fw Time t7 Bw Zone selectivity Selectivity time Enable StartUp StartUp threshold StartUp time Enable Threshold I3 Enable StartUp StartUp threshold StartUp time Enable Curve Threshold I4 Time t4 Enable Trip Zone selectivity Selectivity time Enable StartUp StartUp threshold StartUp time Enable Curve Threshold I4 Time t4 Enable Trip Zone sel
Protection RV Parameter / Function Enable Threshold U10 Time t10 Enable Trip Enable Threshold P11 Time t11 Enable Trip Enable Threshold f12 Time t12 Enable Trip Enable Threshold f13 Time t13 Enable Trip Enable Trip Threshold 1 Enable Threshold Threshold 2 Enable Threshold Threshold lw Enable Threshold RP UF OF OT Load Control ON / OFF ON / OFF ON / OFF ON / OFF ON / OFF ON / OFF ON / OFF ON / OFF ON / OFF ON / OFF ON / OFF ON / OFF Note: for an explanation of the characteristics of the single p
14.5.4. Settings Menu 1/5 Menu Protections Measurements Settings The configuration parameters in the Settings menu are password protected. Among the most significant values you can select, note the neutral threshold (values 50%, 100%, 150%, 200%), the external toroid size (values 100A, 250A, 400A, 800A), the mains frequency at the installation (values 50Hz, 60Hz). For a more detailed description of the settings for the modules, refer to the documentation on the modules (ch. 15).
14.5.4.2.1 Neutral adjustment specifications To adjust neutral (InN) comply with the following formula: I1 x InN ≤Iu. With a 4-pole CB, this setting is checked by the relay which signals any failure by means of a LED (see par. 14.6.1) and adjusts this parameter independently to the accepted limits. With a 3-pole CB, with external neutral, the relay performs no checks and setting is to be done by user. E.g. With E1B800 CB having a 400A Rating Plug, Iu = 800A and I1 = 1In, InN adjustment may be: 50-100-200%.
14.5.5. Test Menu Access to the Test menu is password protected. 4/5 Menu Password Enter Measures Settings 1/6 Test Enter 0*** CB status Auto Test Test Trip Test (disabled) Device test CB open Enter password The menu shows the state of the CB, in the dialog module (COM module) the state of the springs and the position of the CB, and in this submenu you can make the CB open or close. Using the “Trip Test” function lets you view the disabling/enabling of the Trip.
In any case, functionality of the relay is in no way modified by the presence of the wear messages. The prealarm message (wear > 80%, “warning” LED lighting up) indicates that the wear has reached a high value. The alarm message (100% wear, “alarm” LED lighting up) indicates that it is necessary to check the state of contact wear. The percentage of wear depends on the number of openings carried out by the circuit-breaker and by the absolute current interrupted during each of them. 14.6.
Error message Description Notes UF Alarm Alarm for protection UF OF Alarm Alarm for protection OF Load LC1 Alarm for load control LC1 Load LC2 Alarm for load control LC2 L1 Sensor Alarm for L1 phase current sensor Phase L1 sensor disconnected or faulty L2 Sensor Alarm for L2 phase current sensor Phase L2 sensor disconnected or faulty L3 Sensor Alarm for L3 phase current sensor Phase L3 sensor disconnected or faulty Ne Sensor Alarm for Ne phase current sensor Phase Ne sensor disconnecte
Error message Failed 1003/2003 Description Incongruence between thresholds of protectionst L ed S2 (SETA/SETB) Failed 1004/2004 Incongruence between thresholds of protectionst I ed S2 (SETA/SETB) Failed 3001 Inconsistency as to language change Failed 3002 Inconsistency on Rc toroid Failed 3003 Inconsistency as to external Neutral configuratione Exception 6 Control temporarily unavailable Unavailable Function temporarily unavailable Invalid date Date has not been se Parameters revised Progra
N° 18 Situation Invalid date Possible causes 1. First installation 2. Information lost due to power failure Suggestions FN see 14.4.3.1 19 20 21 Untimely trip LED lighting The language cannot be changed see 14.6.3 see 14.6.1 1. Relay remotely set 1. Set locally 2. CB not open 2. Open CB 3. Vaux or PR120/V or PR030/B not installed 3. Power the relay 14.7.1. In the case of a fault 1. 2. 3. 4.
15. Modules 15.1. PR120/V - MEASURING Module 15.1.1. General characteristics The MEASURING module records and processes the phase voltages. The measurements are sent by the module to the protection release, enabling the implementation of a set of protection and measurement functions. The module comes with a “Power” LED and a sealable isolator for dielectric stiffness tests. The module also enables the relay to be powered. 15.1.2. Front view - “Power Line” LED (lit when busbar voltage is On, see 15.1.
PR122/P and PR123/P Relay + PR120/ D-BT - WL-COM Module ENABLING THE UNIT AND ITS FUNCTIONS PR122-PR123/P Relay PR120/D-BT THREE-PHASE (phase-to-phase voltage) Relay display backlighting Enabling threshold 70 Vrms PR122/P and PR123/P Relay + PR120/K Module + PR120/D-BT - WL-COM Module ENABLING THE UNIT AND ITS FUNCTIONS THREE-PHASE (phase-to-phase voltage) PR122-PR123/P Relay PR120/K PR120/D-BT WL Relay display backlighting Enabling threshold 90 Vrms 110 Vrms N.B.
Continues from previous page 7/7 Measurements 6/6 Measurements Main Frequency U Max Contact Wear U Min Waveforms Reset measures Graphics Reset measures Peak factor U Max I1 : --- I3 : --- I2 : --- Ne : --- Main Frequency U Min Jan 10, 2003 04:31 U1 : 416 V 5 min Jan 10, 2003 04:31 U1 : 416 V 5 min 50.0 Hz Measured value Contact Wear 0.0 % (1) 1/7 Waveforms I1 = - - - I1 I2 I3 Current, Harmonics Measurements 21/2 I1 Refresh Total distorsion : Harmonic n.
Continues from previous page Voltage 12 = 416 V Measurements 2/2 U 12 Refresh Total distorsion : Harmonic n. 1/40 : 100.0 % 0.0 % Harmonics Harmonics (1) Valid for PR123 only 15.1.5.2.
Parameter / Function Values 50-60 Hz Mains frequency Contact wear Waveforms Notes Measured value Available in self-supply mode Percentage of contact wear Current I1/I2/I3/Ne Refresh Harmonics Voltage 12/23/31 Refresh Harmonics 15.1.5.4. Measurements Menu 15.1.5.4.1 Historicals 1/7 Measures A whole range of measurements is accessible from the “Measurements/Historicals” menu. Historicals Power factor Energy Trip, measures, log 15.1.5.4.
15.1.5.4.6 Energy The unit also provides meter readings of the total active, reactive and apparent energy of the system. The minimum value that can be displayed is 0.001 MWh or 0.001 MVARh or 0.001 MVAh. The energy meters’ end of scale is approximately 2.15 billion kWh / kVARh / kVAh. The meter can also be reset by pressing the “Reset meters” key on the menu. For the ranges and precisions see par.14.2.9.15.
15.1.7. Electrical characteristics of the transformers If the phase-to-phase line voltage is greater than 690Vac, it is essential to use a step-down transformer between the bars and the PR120/V module. Voltage transformers can be installed up to 15m away from the PR120/V module to which they are connected. Proper operation is only guaranteed for star/star or delta/delta configurations. The allowable primary and secondary rated voltages that must be set on the unit are specified in the table 15.1.5.2.
15.2. PR120/D-M - COM communication module 15.2.1. General characteristics 15.2.2. Front view Dedicated communication module for connecting the relay to a Modbus net, and for remote supervisory and control activities on the circuit-breakers. - “Power” LED (lit when Vaux is installed) - LED RX/TX (data send/receive signal) 15.2.3. Releases complete with the module - optional for PR122/P - optional for PR123/P 15.2.4.
15.3. PR120/K signalling module 15.3.1. General characteristics The module enables the local signalling of alarms and circuit-breaker trips. There are two possible configurations for the SIGNALLING module: - default configuration: 1 digital input, 3 contacts with pole in common, 1 independent contact; - alternative configuration: 4 independent contacts. In this case, the digital input is wired, but not brought up to the terminal block. The two configurations are alternative to each other.
15.3.7. PR120/K module menu The PR120/K is fitted with four relays having contacts named K51/p1, K51/p2, K51/p3 and K51/p4 which can signal different situations selectable by the user from among those given in the standard list, whereas customizations can be programmed by selecting “custom” on the menu and setting the signal required with a PDA, SD-Testbus or PR010/T. See Appendix 16.4. Parameter / Function Relay no. 1...4 Signal source (K51/p1...p4) Delay NO/NC Latch Values Standard or custom 0...
15.3.9. PR120/K module menu layout The menu layout relating to relay no. 1 (K51/p1) is shown below as an example; the same applies to the menus for the other relays. 1/5 Signalling module Relay n.1 Relay n.2 Relay n.3 Relay settings Signalling module 5/5 1/4 Relay n.1 Signal source Relay n.3 Signal source None Relay n.4 Delay L prealarm Input NO / NC 1/13 L timing Input None None Signal source 13/13 Load Lc1 Load Lc2 Latch Custom None Delay 0.
15.4. PR120/D-BT - WL-COM wireless communication module 15.4.1. General characteristics This module enables wireless communication between the protection releases and a handheld PC (PDA) or a laptop with a Bluetooth port. 15.4.2. Front view - “Power” LED (lit with Vaux or PR120/V installed) - LED Rx/Tx (send/receive signal) - LED BT (Bluetooth link enabled 15.4.3. Releases complete with the module - optional for PR122/P - optional for PR123/P 15.4.4.
16. Appendices 16.1. PR021/K outside signalling unit 16.1.1. General information The signalling unit converts the digital signals provided by the protection units into electrical signals by means of normally-open electric contacts. Information on the status of the protection functions transits on a dedicated serial line connected to the release.
16.1.5.1. PR021/K unit menu table Protection PR021K unit Parameter / Function Relay no. 1 / 2 / 3 / 4 / 6 / 7 / 8 Signal source function Values Present Absent Notes Leave as Absent if there is no PR021/K Delay None L Prealarm L Timing S Timing L Trip S Trip G Trip I Trip Any trip Custom 0...100 s step 0,01s NO/NC NO/NC Latch ON/OFF - See par. 16.3.
16.3. Data Logger (recorder) The data logger function is available on the PR122/P and PR123/P units and it can be used to save the instantaneous values of certain analog and digital measurements automatically in a large-sized memory buffer. The data can easily be downloaded from the unit using either the SD-TestBus application via a Modbus bus, and transferred to any personal computer for processing. The function stops the recording every time a trip occurs in order to facilitate failure analysis. 16.3.1.
16.3.2.4. Setting and viewing customized stop events (triggers) From the system, you can set customized stop events (triggers) to coincide with the events shown in paragraph 16.4. In the event of a customized trigger point, the following window is displayed: 5/5 Stop event L Prealarm Any Trip Custom None 16.3.2.5. Setting the stopping delay The stopping delay can be set between 0.00 [s] and 10.00 [s], in 0.01 [s] steps. 4/6 Data logger Sampling freq. Stop delay Enter Stop event 0.
Maximum recording time is established by the sampling frequency set only, as described in the table in paragraph 16.4.2.2; recording time may be lower than maximum time attainable when the sum of stopping delay and time elapsing between a restart trigger and a trigger is lower than the maximum value, as described in the figure below: Recording time Stopping delay Restart Trigger Trigger Maximum recording time 16.3.4. Description of the information given by the Data Logger system 16.3.4.1.
16.3.4.3. Information from the system on the configuration and status of the Data Logger The following information is provided on the status of the data logger: STATUS Waiting trigger: Data Logger triggered: Data Logger stopped: this means that the data logger is enabled and waiting for the occurrence of the event selected as the trigger. this indicates that the trigger event has occurred and the data logger is still recording.
16.4.3. Examples of “Custom” events for the Data Logger function, for PR120/K and PR021/K No. (decimal) 1920 2894 2688 2049 2306 4124 33672 1793 Event G timing L1 or L2 or L3 sensor error or Trip Coil error LC1 alarm G alarm UV timing UV or OV or RV tripped CB connected and springs charged Harmonic distortion > 2,1 Notes PR122 x x x x x x x x PR123 x x x x x x x x You can combine the status bits with “and”/“or” logical functions within the same group of events (byte).
Two toroidal sizes are available: the small toroid can be installed on E1 and E2 three-pole sizes, the medium toroid can be installed on E1 and E2 four-pole sizes and on E3 three-pole sizes. The PR122/P LSIRc unit provides all PR122/P LSI functions but with one addition: protection against residual current faults.
17.
Fixed circuit-breaker Basic version with horizontal rear terminals E4 View A 3 POLES (E4) 4 POLES (E4) 4 POLES(E4/f) E6 View A 3 POLES (E6) 4 POLES (E6) 4 POLES (E6/f) Fig. 36 Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
Fixed circuit-breaker Basic version with vertical rear terminals E1 E2/E4 E1 View A E3/E6 E2 View A E3 View A Captive M12 included in the supply E4 View A E4/f View A E6 View A E6/f View A Captive M12 included in the supply Captive M12 included in the supply Fig. 36a Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc. no.
Fixed circuit-breaker Basic version with front terminals E1 E2 E3 Fig. 37 Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
Fixed circuit-breaker Basic version with front terminals E4 E4 E6 E6 E4/f E6/f Fig. 38 Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc. no.
Fixed circuit-breaker Compartment dimensions Compartment door drilling Depth N° 2 holes for IP54 protection 3 POLES 4 POLES Tightening torque of the main terminals: Nm 70 Tightening torque of the earthing screw: Nm 70 Holes for passing through flexible cables for mechanical interlocks High resistance M12 screw Quantity per terminal PHASE A B E1 400 490 E2 400 490 E3 500 630 E4 700 790 E4/f E6 E6/f - 880 1000 1130 - 1260 NEUTRAL Fig.
Withdrawable circuit-breaker Basic version with horizontal rear terminals E1 E2/E3/E4/E6 4 POLES 3 POLES 3 POLES 4 POLES Legend E1/E2 View A 1 Inside edge of compartment door E3 View A 2 Segregation (where foreseen) 3 POLES 3 POLES 4 POLES 4 POLES 3 Fixing fixed part Ø 10 drilling (use M8 screws) 4 N° 1 M12 screw (E1, E2, E3) or n° 2 M12 screws (E4, E6) for earthing (included in the supply) 5 Run from connected for a TEST to isolated 6 Alternative drilling with 25mm pitch for fixing fixed part
Withdrawable circuit-breaker Basic version with horizontal rear terminals E4 View A 3 POLES (E4) 4 POLES (E4) 4 POLES (E4/f) E6 View A 3 POLES (E6) 4 POLES (E6) 4 POLES (E6/f) Fig. 41 Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
Withdrawable circuit-breaker Basic version with vertical rear terminals E1 E2/E4 E3/E6 E2 View A E1 View A E3 View A Captive M12 included in the supply E4 View A E4/f View A E6 View A E6/f View A Captive M12 included in the supply Captive M12 included in the supply Fig. 42 Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc. no.
Withdrawable circuit-breaker Version with front terminals E1 E2 E3 Fig. 43 Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
Withdrawable circuit-breaker Version with front terminals E4 E4 E6 E6 E4/f E6/f Fig. 44 Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc. no.
Withdrawable circuit-breaker Version with flat terminals E1 E2 E1 View A E4 View A E2 View A E4/f View A E3 View A E6 View A E6/f View A Fig. 45 Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
Withdrawable circuit-breaker Compartment dimensions Compartment door drilling Depth N° 2 holes for IP54 protection 3 POLES 4 POLES Tightening torque of the fixing screws: 20 Nm Tightening torque of the main terminals: 70 Nm Tightening torque of the earthing screw: 70 Nm Holes for passing through flexible cables for mechanical interlocks High resistance M12 screw Quanty per terminal PHASE A B E1 400 490 E2 400 490 E3 500 630 E4 700 790 - 880 E4/f E6 E6/f 1000 1130 - 1260 NEUTRAL
Compartment door mechanical lock Door drilling Minimum distance between the circuit-breaker and the switchgear wall Fixed version Withdrawable version A 3 POLES 4 POLES E1 180 180 E2 180 180 E3 234 234 E4 270 360 - 360 360 486 - 486 E4/f E6 E6/f Fig. 47 Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
18. Circuit diagrams WARNING: Before installing the circuit-breaker, carefully read notes F and O on the circuit diagrams. Operating status shown The circuit diagram is for the following conditions: - withdrawable circuit-breaker, open and racked-in - circuits de-energised - releases not tripped - motor operating mechanism with springs unloaded. Versions The diagram shows a circuit-breaker in withdrawable version; it can be applied to a fixed version circuit-breaker as well.
S75E/1.4 = Contacts for electrical signalling of circuit-breaker in disconnected position (only with withdrawable circuitbreakers) S75I/1..5 = Contacts for electrical signalling of circuit-breaker in connected position (only with withdrawable circuit-breakers) S75T/1..
Fig. 47 Fig. 48 Fig. 61 Fig. 62 = Circuits of the indicator module PR120/K of the PR122/P and PR123/P releases - connection 2 (optional) (see note V). = Circuits of the measuring module PR120/V of the PR122/P and PR123/P releases connected inside the three-pole circuit-breaker with outside neutral conductor (optional for the release PR122/P)(see note U). = SACE SOR TEST UNIT Test/monitoring Unit (see note R) = Circuits of the signalling unit PR021/K (outside the circuit-breaker). 18.3.
Circuit diagram symbols (IEC 60617 and CEI 3-14 ...
Circuit diagram - Operating status Three-pole circuit-breaker with PR121/P, PR122/P or PR123/P electronic release Terminal not connected Four-pole circuit-breaker with PR121/P, PR122/P or PR123/P electronic release Terminal not connected Z) Three-pole circuit-breaker with PR122/P or PR123/P electronic release, residual current protection and U<=690V. Model L2234 L2778 L4681 L5179 L5439 Three-or four-pole switch-disconnector Apparatus Doc. no.
Motor operating mechanism, opening, closing and undervoltage releases Signalling contacts Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
Signalling contacts Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc. no.
Auxiliary circuits of the PR121, PR122 and PR123 releases Warning: see note F W2 (LOCAL BUS) W2 (LOCAL BUS) PR120/V measuring module Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
PR120/D-M communication module W1 (SYSTEM BUS) PR120/K signalling module (+) (-) (+) (+) (-) (-) Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc. no.
PR021/K signalling unit Model L2234 L2778 L4681 L5179 L5439 Apparatus Doc.
L5439 ABB S.p.A. ABB SACE Division Via Baioni, 35 - 24123 Bergamo - Italy Tel.: +39 035.395.111 - Telefax: +39 035.395.306-433 http://www.abb.com 1SDH000460R0002 Due to possible developments of standards as well as of materials, the characteristics and dimensions specified in the present catalogue may only be considered binding after confirmation by ABB SACE.