Specifications

6
OPERATION
1. Place the weighing platform on a level, rigid surface.
2. Press POWER [
] key to turn the unit ON any
weight on platform will be set to zero. (See figures
1-10 for the screen squence while CC240RF turns on).
3. Select the desired units by pressing [LB / KG] key.
4. Place cylinder on scale and connect scale as shown in
Figure-B. Note the weight of the empty tank. Do not
press [TARE] to zero the scale platform.
When recovering refrigerant do not exceed the
maximum tank fill weight. This weight equals the
empty tank weight plus 80% of the water capacity
weight. The water capacity weight is usually stamped
on the tank.
5. Open the cylinder valve and all other valves that are in the recovery pathway. This allows the flow of
refrigerant to the refrigerant recovery unit.
Recovery Mode
Figure - B
Charge Mode
1. Place the weighing platform on a level, rigid surface.
2. Press POWER [
] key to turn the unit ON any
weight on platform will be set to zero. (See figures
1-10 for the screen squence while CC240RF turns
on).
3. Select the desired units by pressing [LB / KG] key.
4. Place cylinder on scale and connect scale as shown
in Figure-A. The display will show the weight of the
Freon
®
plus the weight of the cylinder. Press [TARE]
to zero the scale platform.
5. Open the cylinder valve and all other valves that are in
the charging pathway.
6. The display will show the amount of refrigerant leaving the tank.
7. When the desired amount is reached, close the cylinder valve and the valves in the manifold.
8. Press and hold the POWER [
] key for 4 seconds to turn the unit off.
Figure - A