CPG #2561255  FIRELARM 2500 Operating Manual 
A-4 
A.4  Master Box Module (Model MBM) 
UL LISTED: For use with the FireLarm 2500 
Part No. 345-0235 
Power requirements: 
  Standby: 30mA Max @24VDC 
  Alarm:  300 mA Max @24VCD 
Master Box Coil Resistance: 14.5 ohms 
Trouble output: Positive 2.5 V goes low in trouble and SPDT contacts transfer. 
 Contacts rated 2A@30VDC 
Visual indicators: Yellow - Trouble/Disable 
    Yellow - Reset supervisory/ contacts off normal 
Disable capability: Switch provided (can be made inoperative) 
Size: 3"x5-1/2" 
The Model MBM is a local energy type Master Box actuating module for use with the FireLarm 2500 Fire 
Control Panel. The unit can be mounted in the control panel housing, if space is available, or in a 
separate housing (CPG #327-0089). The circuit between the module and the master box is supervised to 
detect an open circuit. Terminals are provided for the connection of the master box reset supervisory 
contacts. 
A switch is provided to disable the unit so 
that it will not trip the master box. Operation 
of this switch will cause LED (D6) to 
illuminate. To make this switch inoperative, 
remove R42. 
If the master box is provided with reset 
supervisory contacts, the position of these 
contacts may be supervised. When these 
contacts are off normal LED D5 will 
illuminate and the trouble outputs will be 
activated. 
24VDC
.3A MAX.
N.O. (TERMINAL 31)
COM (TERMINAL 30)
TO AUXILIARY
ALARM CONTACTS
CONTACTS SHOWN
IN NORMAL STANDBY
CONDITION
HARRINGTON
OR GAMEWELL
MASTER FIRE
ALARM BOX
TRIP COIL
ORANGE ORANGE
RED
ORANGE
BLUE
WHITE
OPTIONAL RESET
SUPERVISION
CONTACTS
COM - (TERMINAL 43)
TERMINAL 13
TERMINAL 14
290-0016
CONNECT INTO
SUPV. CIRCUIT
WITH 5.1K OHM
END-OF-LINE 
RESISTOR (#024-4556)
AUX PWER + (TERMINAL 44)
RED
GREEN
YELLOW
5.1K
1234
BLACK
YELLOW
MBM
Figure A-5. MBM. 
Figure A-6. MBM Module Wiring. 