Specifications
E
D
C
B
A
CPG #2561255  FIRELARM 2500 Operating Manual 
A-3
A.3  Style Z (Class A) Module for NAC circuits (CAM) 
UL LISTED: For use with the FireLarm 2500  
Part No. 345-0234 
TRANSIENT PROTECTED 
BUILT IN 5.1K END OF LINE RESISTOR 
POWER REQUIREMENTS IN ALARM: Approx. 25mA @ 24VDC from control panel notification 
appliance circuit 
The Model CAM Style Z (Class A) Module is designed to be used with the FireLarm 2500 Fire Control 
Panels to convert a single Style Y (Class B) notification appliance circuit to a Style Z (Class A) circuit (one 
module is required for each notification appliance circuit). The module is provided with snap track which is 
mounted to the cabinet via double-sided foam tape and secured by two #6 sheet metal screws. The 
module should be mounted in the area below the main circuit module as shown below so that the 
terminals are accessible. 
USE FOAM TAPE TO MOUNT SNAP 
TRACK IN CABINET AND SECURE 
WITH TWO #6 SHEET METAL 
SCREWS BEFORE MOUNTING CAM 
MODULE IN SNAP TRACK
1
+
+
32
-
-
+
4
-
EXTERNAL
INDICATING
APPLIANCES
RED
BLACK
TO INDICATING
APPLIANCE CIRCUIT
TERMINALS.
REMOVE EOL RESISTOR
.
POLARITY SHOWN IS FO
R
STANDBY (NON-ALARM)
CONDITION
2
90-0029
CAM
Figure A-4. CAM Module Location.Figure A-3. CAM Module Wiring.