CPG #2561255  FIRELARM 2500 Operating Manual 
A-2 
A.2  Zonal Digital Alarm Communicator Transmitter (2500-ZDACT) 
UL LISTED: For use with the FireLarm 2500 
Transient protected 
Power requirements: 
 Input current  
 Standby:  50mA 
 Alarm current: 90mA max. 
Part # 2500-ZDACT: 
The ZDACT is used for off-premises monitoring of the fire alarm control panel. Signals are sent to a 
Digital Alarm Communicator Receiver (DACR) using either a primary or a secondary telephone line. Both 
telephone lines are supervised; if one line is operational and the other is in trouble, a report is sent to the 
supervising station and the Line Fault trouble LED (D3) is illuminated for local indication. The Panel 
Supervisory trouble LED (D2) will illuminate if communication with the control panel is lost. The ZDACT 
mounts directly on the FACP main board with earth ground lug screwed under standoff nut at top corner 
post. Programming is done through the FACP with inputs for two phone numbers and a 4-digit account 
number. The transmission format is Security Industry Association (SIA) Level 1 and is compatible with 
the receivers listed below. The ZDACT will transmit a test call every 24 hours to the DACR. 
Compatible SIA Level 1 Receivers 
Manufacturer Model Number 
Silent Knight  9500 with 9810 Line card 
Figure A-2. ZDACT Mounting. 