Specifications
Contents 
1 
2 
3 
CPG #2561255  FIRELARM 2500 Operating Manual 
3-4
Table 3-1: Current Requirements. 
  Module/Device  Standby mA  Alarm mA 
2500 with LCD display 
2500 without LCD display 
CAM (Class A module) 
RALCD (Remote Annunciator) 
ZDACT (Digital Alarm Communicator) 
MBM module 
PAM-1 or PAM-2 Relay 
170 
105 
0 
95 
30 
30 
15 
310* 
250 
25 
115 
50 
15 (250 momentary) 
15 
*Includes one zone short circuit current. 
Table 3-2: Secondary Power Requirements. 
NFPA-72 National Fire Alarm Code  Standby Time  Alarm Time 
Local Systems 
Auxiliary Systems 
Remote Station Systems 
Central Station Systems 
24 hrs. 
60 hrs. 
60 hrs. 
24 hrs. 
5 min. 
5 min. 
5 min. 
5 min. 
Table 3-3: Calculation Table. 
1 2 3  4 5  6 
Module/Device  Qty.  Standby mA Per Unit  Total Standby 
Current 
Alarm mA Per Unit  Total Alarm 
Current 
    Total mA    Total mA   
    Convert to A  X 0.001 Convert to A  X 0.001
    Total A    Total A   
    Multiply by hours 
from table 2 
X  AH for 5 mins.  ÷ 12
    Total Standby AH    Total Alarm AH   
        + Total Standby AH   
    Total AH  
        Efficiency Factor  ÷ 0.85
    Required AH  
  Select a battery such that the battery’s amp hour rating meets or exceeds the 
calculated amp hour requirement (44AH maximum). 