101100
200 300 400 500 600 700 1200
400
350
300
250
200
150
100
50
0
800 1000900 1100
2400
2200
2000
1800
1600
1400
1200
1000
800
600
200 300 400 500 600700 1200
96
94
92
90
88
86
84
82
80
800 1000900 1100
1
2
200 300 400 500 600 700 1200
400
350
300
250
200
150
100
50
0
800 1000900 1100
37,5
40
42,5
45
47,5
200 300 400 500 600 700 1200
400
350
300
250
200
150
100
50
0
800 1000900 1100
50
55
60
65
70
200 300 400 500 600 700 1200
400
350
300
250
200
150
100
50
0
800 1000900 1100
37,5
40 42,5
45
47,5
50
RT
ET
OT
IF
EF
FT
CP
F2
F1
HE
CT
BP
BP
IT
CH
PI
PE
SCHEMATIC DIAGRAM
CV 1000
Name of component
F1 Inlet fan
F2 Exhaust fan
IF Fresh air filter
EF Exhaust air filter
BP Bypass damper
HE Countercurrent heat exchanger
CH Comfort heating surface
CT Condensate tray
CP Condensate pump
FT Float
RT Room temperature sensor
OT Outdoor temperature sensor
ET Exhaust temperature sensor
IT Inlet temperature sensor
PRODUCT INFORMATION CV 1000
SOUND ENERGY LEVEL  PRESSURE SIDE
L
W
= L
WA
+ K
W
HZ
ZONE 1
K
W
ZONE 2
K
W
63
-4 -5
125
-9 -4
250
-5 -7
500
-12 -13
1000
-15 -16
2000
-13 -15
4000
-20 -22
8000
-20 -29
Sound energy level for ducts is stated according to: EN ISO 5136
SOUND ENERGY LEVEL  CABINET
L
W
= L
WA
+ K
W
HZ
ZONE 1
K
W
ZONE 2
K
W
63
13 13
125
8 11
250
6 6
500
-7 -9
1000
-12 -16
2000
-14 -16
4000
-20 -18
8000
-20 -17
Sound energy level from the cabinet is stated according to: EN ISO 3744
SOUND ENERGY LEVEL  SUCTION SIDE
L
W
= L
WA
+ K
W
HZ
ZONE 1
K
W
ZONE 2
K
W
63
-2 -2
125
-9 -7
250
-8 -9
500
-18 -19
1000
-21 -22
2000
-25 -28
4000
-36 -38
8000
-42 -49
Sound energy level for ducts is stated according to: EN ISO 5136
SOUND ENERGY LEVEL  CABINET (dB(A))
SFP W/(m
3
/s)*
TEMPERATURE EFFICIENCY RATIO (%)
Add extra pressure loss for F7 inlet filter.
ΔP = 0,0222 ∙ q
v
[Pa]; (q
v
= flow i m
3
/h)
Pressure loss (p) incl. F7 filter: p = p
S
+ Δp [Pa]
Power consumption (P):
P = SFP ∙ q
v
/3600 [W];
(SFP from diagram and q
v
= flow i m
3
/h)
* Specific electricity consumption for air transport.
Stated for both fans and control system.
1: According to: EN308 (without condensation)
Conditions: Indoor air: 25 °C 28 % RH
Outdoor air: 5 °C 50 % RH
2: With condensation
Conditions: Indoor air: 25 °C 55 % RH
Outdoor air: -10 °C 50 % RH
SOUND ENERGY LEVEL  PRESSURE SIDE (dB(A))
SOUND ENERGY LEVEL  SUCTION SIDE (dB(A))
Airow (m
3
/h)
Airow (m
3
/h)
Airow (m
3
/h)
Airow (m
3
/h)
Airow (m
3
/h)
Zone 1
Zone 2
Zone 1
Zone 2
Zone 1
Zone 2
EXTRACTION
INTAKE
INLET
EXHAUST