Technical data

6160
AMP 900
PRODUCT INFORMATION AMP 900
Decentralised ventilation gives you
the freedom to change your mind.
The ventilation can be easily
recongured if the rooms are to be
used for a different purpose.
The AMP 900 is available in
two main models: mixer and
forced ventilation. The unit
is designed to either act as
a mixer or forced ventila-
tion unit, depending on room
configuration and use. The unit
can be placed on the floor or
discreetly between cupboards,
as an integrated part of the
room.
The AMP 900 is designed for
larger rooms, such as class-
rooms, meeting rooms and
open plan ofces.
TECHNICAL DATA
Normal capacity, mixing 690 m³/h at 30 dB(A)
830 m³/h at 35 dB(A)
Normal capacity, displacement 650 m³/h at 30 dB(A)
800 m³/h at 35 dB(A)
Mixing, throw (0.15 m/s) Adjustable grille, 1/1, 7 m v/ 830 m³/h
Adjustable grille, 1/1, 6 m v/ 700 m³/h
Adjustable grille, 2/3, 12 m v/ 850 m³/h
Adjustable grille, 2/3, 9 m v/ 700 m³/h
Adjustable grille, 1/2, 12 m v/ 700 m³/h
Displacement, near zone (0.15 m/s) Near zone from fitting, approx. 1.5 m v/800 m³/h
Near zone from fitting, approx. 1.2 m v/650 m³/h
Electrical connection 1 ~ 230 V, 50 Hz, N + PE
Duct connection Ø315 mm
Condensate drain Ø16 mm
Weight 180 kg
Heat exchanger 3 x countercurrent exchanger (plastic)
Filter F5 standard, F7 option
Colour RAL 9010 (white)
Current 1.8 A
Supply cable 1.5 mm²
Max. power consumption 240 W
Leakage current
<
6 mA
WATER HEATING SURFACE
OPTION
Max. operating temperature 90°C
Max. operating pressure 10 bar
Heating capacity 991 W*
Pipe connection 1/2" (DN 15)
Material of pipes/louvres Cobber/aluminium
Opening/closing time, motorised valve < 60 s
* Capacity at: supply/return temperature 60/40°C, water volume 33 L/h
ELECTRIC HEATING SURFACE
OPTION
PREHEATING COMFORT HEATING
Electrical connection, internal 1 x 230 V 1 x 230 V
Heating capacity 1500 W 1050 W
Thermal cut-out, aut. reset 70°C 70°C
Thermal cut-out, man. reset 120°C 120°C