Technical data

5554
PRODUCT INFORMATION AML 800 / AMP 800
Human beings are sensitive to
changes in the air: There has to
be a natural equilibrium
between the temperature,
oxygen and CO
2
content for
us to feel comfortable.
AML 800 / AMP 800
This ventilation unit is de-
signed for large rooms with
moderate requirement and is
thus perfect for classrooms.
Horizontal or vertical models
will be used depending on the
room and location of the unit.
The unit is available with a
separate control panel, but can
also be connected to a central
control system.
A cooling module can be con-
nected (see page35).
Ducts can also be connected
for extraction or inlet.
TECHNICAL DATA
Max. capacity at 30 dB(A) 650 m³/h
Max. capacity at 35 dB(A) 725 m³/h
Throw (0,15 m/s) 6.5 m at 500 m³/h
7.4 m at 600 m³/h
8.1 m at 700 m³/h
Electrical connection 1 ~ 230 V + N + PE / 50 Hz
Duct connection Ø315 mm
Condensate drain Ø16 mm
Weight 147 kg
Heat exchanger 2 x countercurrent exchanger
(alu)
Filter F5 standard, F7 option
Colour Panels RAL 9010 (white)
Current 1.1 A
Supply cable 1.5 mm²
Recommended min. fuse 13 A
Max. power consumption 156 W
Leakage current
<
6 mA
WATER HEATING SURFACE OPTION
Max. operating temperature 90°C
Max. operating pressure 10 bar
Heating capacity 943 W*
Pipe connection 1/2" (DN 15)
Material of pipes/louvres Copper/aluminium
Opening/closing time, motorised valve < 60 s
* Capacity at: supply/return temperature 60/40°C, water volume 32 L/h
ELECTRIC HEATING SURFACE
OPTION
PREHEATING COMFORT HEATING
Electrical connection, internal 1 x 230 V 1 x 230 V
Heating capacity 1500 W 1000 W
Thermal cut-out, aut. reset 70°C 70°C
Thermal cut-out, man. reset 120°C 120°C
STANDARD AND OPTIONS
AML 800 V AML 800 H AMP 800 V AMP 800 H
Bypass
Electric preheating surface
Electric comfort heating surface
Water heating surface (comfort heating)
CO
2
-sensor (wall-mounted)
CO
2
-sensor (integrated)
PIR/motion sensor
Hygrostat
Condensate pump
Insulated condensate tray
Cooling module
Motorised exhaust damper
x x x x
Motorised main damper
x x x x
Countercurrent heat exchanger (alu)
x x x x
Capacitive return for motor-driven main damper
Energy Meter
x:standard•:option–:notavailable