Technical data
4948
Investigations repeatedly
conrm that poor indoor
climate inhibits learning –
as do noisy ventilation systems.
AML 500 / AMP 500
PRODUCT INFORMATION AML 500 / AMP 500
This ventilation unit is desig-
ned for medium-sized rooms.
Horizontal or vertical models
will be used depending on the
room and location of the unit.
The unit is available with a
separate control panel, but can
also be connected to a central
control system.
A cooling module can be con-
nected (see page35).
Ducts can also be connected
for extraction or inlet.
TECHNICAL DATA
Max. capacity at 30 dB(A) 430 m³/h
Max. capacity at 35 dB(A) 550 m³/h
Throw (0,15 m/s) 5 m at 350 m³/h
5.9 m at 450 m³/h
7,5 m at 550 m³/h
Electrical connection 1 ~ 230 V + N + PE / 50 Hz
Duct connection Ø250 mm
Condensate drain Ø16 mm
Weight 100.6 kg
Heat exchanger Countercurrent exchanger (alu)
Filter F5 standard, F7 option
Colour Panels RAL 9010 (white)
Current 1.1 A
Supply cable 1.5 mm²
Max. power consumption 132 W
Leakage current
<
–
6 mA
WATER HEATING SURFACE OPTION
Max. operating temperature 90°C
Max. operating pressure 10 bar
Heating capacity 686 W*
Pipe connection 3/8" (DN 10)
Material of pipes/louvres Copper/aluminium
Opening/closing time, motorised valve < 60 s
* Capacity at: supply/return temperature 60/40°C, water volume 25 L/h
ELECTRIC HEATING SURFACE
OPTION
PREHEATING COMFORT HEATING
Electrical connection, internal 1 x 230 V 1 x 230 V
Heating capacity 1000 W 630 W
Thermal cut-out, aut. reset 70°C 70°C
Thermal cut-out, man. reset 120°C 120°C
STANDARD AND OPTIONS
AML 500 V AML 500 H AMP 500 V AMP 500 H
Bypass
• • • •
Electric preheating surface
• • • •
Electric comfort heating surface
• • • •
Water heating surface (comfort heating)
• • • •
CO
2
-sensor (wall-mounted)
• • • •
CO
2
-sensor (integrated)
• • • •
PIR/motion sensor
• • • •
Hygrostat
• • • •
Condensate pump
• • • •
Cooling module
– – – •
Motorised exhaust damper
• • x x
Motorised main damper
x x x x
Countercurrent heat exchanger (alu)
x x x x
Capacitive return for motor-driven main damper
• • • •
Energy Meter
• • • •
x:standard•:option–:notavailable