Technical data
4342
Once the temperature and CO
2
level
of the room become too high, the sense of
well-being decreases and productivity drops.
There is also an increased risk
of absence through illness.
AML 300 / AMP 300
PRODUCT INFORMATION AML 300 / AMP 300
This ventilation unit is ideal
for office buildings and
institutions.
A Virtual Preheater (VPH) can
be used. VPH uses a bypass to
divert some of the cold outdoor
air past the heat exchanger
and directly to the heating
element. This protects the unit
against frost, even at very low
temperatures.
A cooling module can be con-
nected (see page35).
Ducts can also be connected
for extraction or inlet.
TECHNICAL DATA
Max. capacity at 30 dB(A) 240 m³/h
Max. capacity at 35 dB(A) 300 m³/h
Throw (0,15 m/s) 4.8 m at 160 m³/h
5.7 m at 220 m³/h
6.5 m at 300 m³/h
Electrical connection 1 ~ 230 V + N + PE / 50 Hz
Duct connection Ø200 mm
Condensate drain Ø16 mm
Weight 49.8 kg
Heat exchanger Countercurrent exchanger (alu)
Filter F5 standard, F7 option
Colour Panels RAL 9010 (white)
Current 0.6 A
Supply cable 1.5 mm²
Max. power consumption 100 W
Leakage current
<
–
3 mA
WATER HEATING SURFACE OPTION
Max. operating temperature 90°C
Max. operating pressure 10 bar
Heating capacity 343 W*
Pipe connection 3/8" (DN 10)
Material of pipes/louvres copper/aluminium
Opening/closing time, motorised valve < 60 s
* Capacity at: supply/return temperature 60/40°C, water volume 15 L/h
ELECTRIC COMFORT HEATING SURFACE OPTION
Electrical connection, internal 1 x 230 V
Heating capacity 1500 W
Thermal cut-out, aut. reset 70°C
Thermal cut-out, man. reset 120°C
STANDARD AND OPTIONER
AML 300 V AML 300 H AMP 300 H
Bypass
• • •
Electric preheating surface
– – –
Electric comfort heating surface
• • •
Water heating surface (comfort heating)
• • •
CO
2
-sensor (wall-mounted)
• • •
CO
2
-sensor (integrated)
• • •
PIR/motion sensor
• • •
Hygrostat
• • •
Condensate pump
• • •
Cooling module
– – •
Motorised exhaust damper
– – –
Motorised main damper
x x x
Countercurrent heat exchanger (alu)
x x x
Capacitive return for motor-driven main damper
– – –
Energy Meter
• • •
x:standard•:option–:notavailable