Technical data
3534
CONTROLS
Airmaster's comfort-creating cooling module
for horizontal models completes the most
exible ventilation system on the market.
AUTOMATIC BYPASS
If the inlet temperature exceeds the level set, the
Airlinq control system will gradually open the by-
pass. Cooler outdoor air will be allowed to bypass the
counterflow heat exchanger, ensuring that the inlet
temperature set is maintained.
Airlinq will adjust the inlet temperature to achieve a hig-
her cooling effect. If the room temperature exceeds the
level set, e.g. as a result of strong sunshine, the bypass
will open automatically.
If a cooling module is fitted to the ventilation unit,
Airlinq will activate it automatically if cooling using
outdoor air is insufficient. When the cooling module
is working, the bypass is still used to regulate the inlet
temperature.
NIGHT TIME COOLING
If the room temperature exceeds the maximum level
set during the day, all Airmaster ventilation units can
automatically cool down the room using colder night
air. We call this function "night time cooling". It will be
registered by the Airlinq control system, and started
automatically. If necessary, the function will use the
bypass damper and cooling module to achieve the
cooling effect required. The building and its contents
will be cooled, and room temperature will reach a
lower level than otherwise obtainable.
COOLING USING THE
COOLING MODULE
The automatic bypass function and night time cooling
ensure that the inlet and room temperature are kept
down. If this is insufficient, effective temperature redu-
ction can be achieved using a cooling module. Airlinq
automatically activates the cooling module, which
reduces the outdoor air's temperature by up to 15°C.
Outdoor air is then supplied to the ventilation unit,
enabling the inlet temperature to be maintained using
the automatic bypass function at the level set.
SPECIALLYDEVELOPED
COOLING MODULE
Airmaster's specially-developed cooling modules (CC)
are controlled fully automatically by Airlinq. Combined
with 5 different network modules (LON
®
, MODBUS
®
RTU RS485, BACnet
TM
M S / T P, B ACn e t
TM
/ I P, K N X
®
) and
the intuitive control panels, Airlinq provides an effi-
cient, economic and long-term ventilation solution.
The cooling module is designed to reduce the outdoor
air temperature by up to 15°C. The units are dimen-
sioned according to European conditions (outdoor
temperature 35°C, 40% relative humidity) according
to standard DS/EN 14511-2. The cooling module is
exempt from the directive for pressure equipment
(PED) according to article 1, part 3.6.
A condensate pump is built in as standard equipment
for all cooling modules.
CONTROL PROCESSES
FOR COOLING
CC COOLING MODULE
is available for the following
ventilation units:
AMP 300 H
AMP 500 H
AMP 800 H
AM ventilation unit
Front panels
Wall frame
Side panels
Cooling module