Direct Vent Gas Stove Owner's Manual

VENT GRAPH (cont'd)
Note: Maximum propane horizontal vent run is 13' (3960mm) when the vertical vent rise is 10' (3048mm)
Note: Minimum vertical rise is 2' (908 mm)
Note: Minimum horizontal run is 11" (279mm) on a vertical to horizontal installation.
Note: Minimum wall thickness 4" (100mm)
Note: Maximum wall thickness 20" (508mm).
FIGURE 19: BAYVUE DV VENT GRAPHS, MODEL DV 30
A vent shall not terminate:
A. Within six feet (1.8 meters) of a mechanical air supply inlet to a building.
B. Above a utility meter within three feet (1 meter) horizontally of its vertical center line.
C. Within six feet (1.8 meters) of any gas service regulator vent outlet.
Version 1.0h
29
24 6810
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
12 14 16
VENTING GRAPH FOR
DV 30 NATURAL GAS
24 68 10
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
12 14 16
VENTING GRAPH FOR
DV 30 PROPANE
VENT TERMINATION MUST FALL IN THE GREY AREA