Technical data

85
LevelWave LR01HB EML3020 A-(en)
ERR 206 Sensor Microwave failure 1 The device's hardware is
defective.
Replace the signal
converter.For more data, refer
to How to turn or remove the
signal converter on page 35.
ERR 207 Sensor Memory failure 1 The device's hardware is
defective.
Replace the signal
converter.For more data, refer
to How to turn or remove the
signal converter on page 35.
ERR 208 Sensor Voltage failure 3 The device's hardware is
defective.
Do a check of the power supply
at the device terminals. Make
sure that voltage values are in
the specified limits in menu
item 2.2.2 DIAGNOSTIC
(Configuration mode /
Supervisor menu). If the
voltage is correct, replace the
signal converter. For more data
on how to replace the signal
converter, refer to How to turn
or remove the signal converter
on page 35.
ERR 210 Sensor Not compatible 1 The software version of the
sensor is not compatible with
the software version of the
signal converter.
Go to menu 1.1.0 IDENT. in
Configuration mode. Record
the version numbers of the
device software given in menu
items 1.1.2, 1.1.3 and 1.1.4.
Give this data to the supplier.
1 Defective wiring.
Out of specification (NE 107 status signal)
ERR 102 Temperature Out of Range 1 The ambient temperature is
outside the given range. This
can cause loss or corruption of
data.
Measure the ambient
temperature. De-energize the
device until the ambient
temperature is back in the
given range. If the temperature
does not stay in the correct
range, make sure that there is
insulation around the signal
converter. If this error occurs 2
times, replace the device.
ERR 201 Overfill 2 The level is in the blocking
distance. There is a risk that
the product will overflow and/or
cover the device.
Remove some of the product
until the level is below the
blocking distance.
ERR 203 Peak Lost 2 The signal peak is not found
within the measuring window
that filters the signals received
by the antenna. The
measurement is not correct.
The device will automatically
increase this window to find the
correct signal.
Do a check of the device, tank
and the process and make
sure that the data agrees with
the device configuration. If
necessary, record a new empty
spectrum. Follow the
instructions on page 79. If
necessary, speak to the
supplier.
Maintenance (NE 107 status signal)
- Empty Spectrum Invalid 5 The empty spectrum stored in
the device does not agree with
the installation. If you change
the device configuration (tank
height etc.), this message will
be shown. The recorded empty
spectrum will not be used by
the device while this error
message is shown.
1
Record a new empty spectrum.
Follow the instructions on page
79.
Error
code
Error Message Status
marker
shown
Cause Corrective action