Technical data

76
HB EML3020 A-(en)LevelWave LR01
How to change from multidrop to point-to-point mode
• Enter the supervisor menu.
• Push [>], 5 × [] and [>] to go to menu item ADDRESS (2.6.1).
• Push [>] to change the value. Enter the value 0 and push [^] to confirm.
• Push [^] to go back to the "STORE" screen.
• Push [] or [] to set the screen to STORE YES and push [^].
i The output is set to point-to-point mode. The current output changes to a range of 4...20 mA
or 3.8...20.5 mA (this range is set in menu item RANGE I (2.4.2)).
6.4.5 Distance measurement
The device displays distance measurements when the output function is set to
"Distance". Menu items related to distance measurement are:
Output Function (2.4.1)
Tank Height (2.3.1)
Blocking Distance (2.3.2)
For more data about the menu items, refer to Function description on page 65, table 2.
Supervisor menu.
CAUTION!
If the distance for 4 mA is set in the blocking distance, the device will not be able to use the full
current output range.
Figure 6-4: Distance measurement
1 Tank Height (2.3.1)
2 Blocking Distance (2.3.2)
3 4 mA Setting (2.4.3)
4 20 mA Setting (2.4.4)
5 Maximum effective measuring range
6 Non-measurement zone