Technical data

73
LevelWave LR01HB EML3020 A-(en)
[>] to change Scale 4 mA.
[>] to change the position of the cursor.
[] to decrease the value or [] to
increase the value.
[^] to confirm.
Use this step to give the 4 mA output
setting (0% limit) in the tank. Refer to the
illustrations that follow. Illustration 1 shows
the settings for level. Illustration 2 shows
the settings for distance.
[>] to change Scale 20 mA.
[>] to change the position of the cursor.
[] to decrease the value or [] to
increase the value.
[^] to confirm.
Use this step to give the 20 mA output
setting (100% limit) in the tank. Refer to the
illustrations that follow. Illustration 1 shows
the settings for level. Illustration 2 shows
the settings for distance.
[] or [] for the selection of the error
delay (0 s, 10 s, 20 s, 30 s, 1 mn, 2 mn,
5 mn or 15 mn).
[^] to confirm.
The time after which the current output
changes to an error value. The error value
shows that there is a measurement error.
[>] to change the tag name.
[>] to change the position of the cursor.
[] to decrease the alphanumeric value
(A, B, ..., 1, 2, ...) or [] to increase the
alphanumeric value.
[^] to confirm.
The device has an identification code (tag
name). The supervisor can enter a
maximum of 8 numbers or letters.
[^] to confirm.
[] or [] for the selection of the save
option (STORE NO or STORE YES).
[^] to confirm.
Set to STORE YES to save and use the
data. Set to STORE NO to cancel the
changes to the device settings.
Screen Steps Description