Technical data

60
HB EML3020 A-(en)LevelWave LR01
6.3 Configuration mode
6.3.1 General notes
Change the settings of your device in Configuration mode. Data about the menus is given on
page 65. You can:
•Use the 1.0.0 INFORMATION menu to read settings, device software versions and error
records. For more data about the Information menu, refer to Table 1: Info.
•Use the 2.0.0 SUPERVISOR menu to commission the device, to run diagnostic tests, set up a
conversion table for volume, mass or flow rate measurement, change critical parameters for
difficult process conditions, reset the device and change basic parameters (tank height etc.),
output settings, HART Address etc. For more data about the Supervisor menu, refer to Table
2: Supervisor.
6.3.2 How to get access to the commissioning menu
Do the steps that follow:
• Push the [>] button.
i This shows the Information menu. The Information menu is read only and does not have
password security.
• Push the [] button one time to scroll up to the Supervisor menu.
i The screen shows the text "2.0.0 SUPERVISOR".
• Push the [>] button one time.
i The screen shows a line. You must enter the password. Push the buttons under the display
screen 6 times (in total and in a given order) to to get access to Configuration mode.
• Type in the password. The factory-set password is [>], [^], [], [], [>] and [^].
i The device shows the text "2.1.0 COMMISSION.".
• Push [>]. Do the basic configuration of the device in the "'Parameters" menu. For more data on
the procedure, refer to Quick Setup (Parameters) on page 72. Push [^] at the end of each step
of the procedure to continue to the next step.
• Push [] to go to menu item 2.1.2 EMP.SPEC.REC. Push [>] to start the empty spectrum
recording procedure. For more data, refer to Function description on page 65, Table 2:
Supervisor.
INFORMATION!
It is not possible to enter the 3.0.0 SERVICE and 4.0.0 MASTER menus. These menus are for
factory calibration and approved personnel only.
CAUTION!
SIL-approved devices: For data about critical device parameters for SIL approval, refer to the
Safety Manual (SIL approval).
INFORMATION!
HOW TO SET THE SUPERVISOR PASSWORD TO "ON" OR "OFF"
The supervisor password is set to "on" by default. If it is necessary to set this function to "off",
refer to Function description on page 65, Table 2: Supervisor menu, menu item PSWD YES/NO
(2.7.4).
INFORMATION!
HOW TO CHANGE THE SUPERVISOR PASSWORD
You can change the password for the supervisor menu. For more data, refer to Function
description on page 65, Table 2: Supervisor menu, menu item PASSWORD (2.7.5).