Technical data

42
HB EML3020 A-(en)LevelWave LR01
• Put the cover on the housing and push it down.
• Turn the cover clockwise until it is fully engaged.
• Tighten the lock screw.
4.2.2 Remote version
For more electrical installation data, refer to Compact version on page 40.
Figure 4-4: How to close the terminal compartment cover
Terminals for electrical installation
Figure 4-5: Terminals for electrical installation
1 Grounding terminal in the housing (if the electrical cable is shielded)
2 Current output -
3 Current output +
4 Location of the external grounding terminal (on the wall support)
INFORMATION!
Electrical power to the output terminal energizes the device. The output terminal is also used for
HART
®
communication.
CAUTION!
Use the applicable electrical cables with the cable glands.
Make sure that the power supply does not have a current more than 5 A or that there is 5 A-
rated fuse in the electrical circuit that energizes the device.
Make sure that the polarity of the power supply is correct. If the polarity is incorrect, you will
not cause damage to the device but the device will not operate.