can assume the follow values:
61 - for 45xx at NATURAL gas;
62 - for 45xx at LP gas;
can assume the follow values:
00 - 230Vac, 50Hz, °C;
01 - 230Vac, 50Hz, °F;
02 - 120Vac, 60Hz, °C;
03 - 120Vac, 60Hz, °F
16 - MENU’S FLOW CHART
CAUTION!!! Changing these
parameters could cause the boiler
and therefore the system to
malfunction. For this reason, only a
qualified technician who has in-
depth knowledge of the boiler
should change them.
The boiler’s micro-processor makes
this menu of parameters available to
the qualified technician for the setting
of the appliance .
Basic functionalities selection and Speed
blower selection (see below for more
explications)
Main electrical supply and temperature unit
selection (see below for more explication)
Domestic functionalities selection. Must be
always at 00
Master or slave selection in a batterie
configuration. Must be always at 00.
Rotating selection in a batterie configuration.
Must be always at 00.
To enter this menu you must:
shut Off the main electrical supply;
move the switch n° 7 (see figure 22,
item “D”) to the ON position;
lite On the main electrical supply.
Now ty is displayed. Use plus and
minus keys to change the value; use
RESET key to save the value and
swap to the next parameter.
To exit this menu you must:
shut Off the main electrical supply;
move the switch n° 7 (see figure 22,
item “D”) to the Off position;
can assume the follow values:
00, 01 and 02. Must be always at 00.
If readable, can assume the follow values:
00, 01, 02, 03, 04, 05, 06, 07 and 08. Must be always
at 00.
If readable, can assume the follow values:
00, 01, 02, 03, 04, 05, 06, 07 and 08. Must be always
at 00.