D TROUBLESHOOTING
PROBLEMS CAUSES CHECKS (IF NECESSARY) REMEDIES
(IF NECESSARY)
the pilot li
g
ht of power switch is off there isnt electrical suppl
y
check the electrical suppl
y
level restore the electrical suppl
y
the fuse doesnt work check the fuse replace the fuse
the power switch is off check that the power switch is on turn the power switch on
the power switch doesnt work check the power switch operatin
g
replace the power switch
pilot li
g
ht of power switch doesnt
work
check the pilot li
g
ht of power switch
operatin
g
replace the power switch
the transformer lamp control,
(
DL8
)
, is off
115V isnt reachin
g
the transformer
input
check the transformer has 115V
input
restore the electrical suppl
y
the transformer doesnt work
check the transformer has 24V
output
replace the transformer
the DL8 doesnt work check DL8 operatin
g
replace the electrical control board
the heater temperature lamp
control,
(
DL1
)
is off
the heater temperature control
contacts are open
check that the heater has the
required temperature
increase the heater temperature
set
24V isnt reachin
g
C contact of
heater temperature control
check 24V presence on C heater
temperature control contact
restore the electrical connection
the heater temperature control
doesnt work
check heater temperature control
operatin
g
replace the heater temperature
control
the DL1 doesnt work check DL1 operatin
g
replace the electrical control board
the low water cutoff lamp control,
(
DL2
)
, is off
there isnt enou
g
h water in the
heater
check theres enou
g
h water in the
heater
restore the water ri
g
ht level in the
heater
low water cutoff doesnt work check the low water cut-off
operatin
g
replace the low water cut-off
DL2 doesnt work check DL2 operatin
g
replace the electrical control board
the NC pressure switch lamp control,
(
DL3
)
,
is off
24V isnt reachin
g
the C contact
of pressure switch
check theres 24V on the C
contact of pressure switch
restore 24V on the C contact of
pressure switch
pressure switch contact is on NO check the flue
g
as dischar
g
e fan is
off
replace pressure switch
DL3 doesnt work check DL3 operatin
g
replace electrical control board
the NO pressure switch lamp
control,
(
DL4
)
, is off
flue
g
as dischar
g
e fan is off
check the flue
g
as dischar
g
e fan is
on
replace the flue
g
as dischar
g
e fan
115V isnt reachin
g
the flue
g
as
dischar
g
e fan
check 115V is reachin
g
the flue
g
as dischar
g
e fan contacts
restore the electrical suppl
y
pressure switch contact is on NC check the pressure switch
operatin
g
replace the pressure switch
DL4 doesnt work check DL4 operatin
g
replace the electrical control board
the i
g
nition module lamp control,
(
DL7
)
, is off
24V isnt reachin
g
i
g
nition module check 24V is reachin
g
i
g
nition
module contacts
restore 24V
DL7 doesnt work check DL7 operatin
g
replace the electrical control board
the
g
as valve lamp control,
(
DL5
)
,
is off
24V isnt reachin
g
g
as valve check 24V is reachin
g
g
as valve
contacts
replace i
g
nition module
DL5 doesnt work check DL5 operatin
g
replace the electrical control board
the room thermostat lamp control,
(
DL6
)
, is off
room thermostat contacts are
open,
(
if an
y)
check room thermostat operatin
g
replace the room thermostat
room thermostat doesnt work,
(
if
an
y)
check room thermostat operatin
g
replace the room thermostat
DL6 doesnt work check DL6 operatin
g
replace the electrical control board
the circulator pump switch li
g
ht is
off
circulator pump switch is off check heater temperature is hi
g
her
than 140°F
check heater temperature is hi
g
her
than 140°F
dhw priorit
y
thermostat contacts
are open
check heater temperature is hi
g
her
than 140°F
increase the heater temperature,
(
if
necessar
y)
room thermostat contacts are open check room thermostat operatin
g
replace the room thermostat
circulator pump switch li
g
ht doesnt
work
check circulator pump switch li
g
ht
operatin
g
replace the circulator pump switch