Owner Manual
• To eliminate the risk of burns or fire by
reaching over heated surface units, cabinet 
storage space located above the surface units 
should be avoided. If cabinet storage is to be 
provided, the risk can be reduced by installing 
a range hood or microwave hood combination 
with minimum 400 CFM that projects 
horizontally a minimum of 5" (12.7 cm) beyond 
the bottom of the cabinets. (See Figure 1) 
•
If a range hood is installed above the
appliance, maintain a 30” minimum clearance 
between cooking surface and bottom of range 
hood. The range hood must be connected 
directly to flues or to the outside. (See Figure 
1) 
•
Avoid placing cabinetry directly above
the appliance when possible. If cabinetry is 
used above the cooking surface, use cabinets 
no more than 13″ deep. Make sure the wall 
coverings, countertop and cabinets around the 
appliance can withstand heat up to 200º F 
(93°C) generated by the appliance. (See 
Figure 1) 
•
Cabinet opening dimensions that are
shown must be used. Given dimensions are 
minimum clearances. (See Figure 1) 
•
Working areas adjacent to the range
should have 18″ minimum clearance between 
countertop and cabinet bottom. (See Figure 1) 
•
All openings in the wall or floor where
range is to be installed must be sealed. 
•
Contact a qualified floor covering installer
to check that the floor covering can withstand 
at least 200°F (93°C). 
•
Use an insulated pad or ¼" (0.64 cm)
plywood under range if installing range over 
carpeting. 
•
The floor anti-tip bracket must be
installed. To install the anti-tip bracket shipped 
with the range, see “Install Anti-Tip Bracket” 
section. 
•
Grounded electrical supply is required.
See “Electrical Requirements” section. 
•
Proper gas supply connection must be
available.  See “Gas Supply Requirements” 
section. 
11










