Installation Guide
18 
Gas shutoff valve: 
A manual gas line shut-off valve must be installed in an easily accessible 
location. Do not block access to shut-off valve. The valve is for turning on or 
shutting off gas to the range. 
GAS PRESSURE REGULATOR 
The gas pressure regulator supplied with this range must be used. The inlet 
pressure to the regulator should be as follows for proper operation: 
Contact local gas supplier if you are not sure about the inlet pressure. 
Burner Input Requirements 
Input ratings shown on the model/serial rating plate are for elevations up to 
2,000 ft (609.6 m). 
For elevations above 2,000 ft (609.6 m), ratings are reduced at a rate of 4% 
for each 1,000 ft (304.8 m) above sea level (not applicable for Canada). 
GAS SUPPLY PRESSURE TESTING 
Gas supply pressure for testing regulator must be at least 1" (2.5 cm) water 
column pressure above the manifold pressure shown on the model/serial 
rating plate. 
Line pressure testing above 0.5 psi gauge (14" WCP) 
The range and its individual shutoff valve must be disconnected from the gas 
supply piping system during any pressure testing of that system at test 
pressures in excess of 0.5 psi (3.5 kPa). 
Line pressure testing at 0.5 psi gauge (14" WCP) or lower 
The range must be isolated from the gas supply piping system by closing its 
individual manual shutoff valve during any pressure testing of the gas supply 
piping system at test pressures equal to or less than 1/2 psi (3.5 kPa). 
a b c
Gas Supply Line
Shutoff Valve "Open" Position
To Range
a
b
c
Natural gas  LP gas 
Minimum pressure  4" WCP  10" WCP 
Maximum pressure  7" WCP  11" WCP 