GAS SUPPLY PRESSURE TESTING 
Gas supply pressure for testing regulator must be at least 1" (2.5 cm) water 
column pressure above the manifold pressure shown on the 
model/serial/rating plate. 
Line pressure testing above 0.5 psi gauge (14" WCP) 
The range and its individual shut-off valve must be disconnected from the gas 
supply piping system during any pressure testing of that system at test 
pressures in excess of 0.5 psi (3.5 kPa). 
Line pressure testing at 0.5 psi gauge (14" WCP) or lower 
The range must be isolated from the gas supply piping system by closing its 
individual manual shut-off valve during any pressure testing of the gas supply 
piping system at test pressures equal to or less than 1/2 psi (3.5 kPa). 