Rigid Pipe Connection 
Since the range must be pulled away from the installation space to provide 
access to the gas regulator connections, and because hard piping restricts 
movement of the range, the range can only be installed using a CSA 
International-certified flexible metal appliance connector. 
If local codes require a hard-piped connection, a combination of pipe fittings 
must be used to connect the range to the existing gas line and maintain an 
accessible working space behind the range. Consult with a qualified local 
technician for an optimal connection suitable for your installation. 
Gas Shut-off Valve 
A manual gas line shut-off valve must be installed in an easily accessible 
location. Do not block access to shut-off valve. The valve is for turning on or 
shutting off gas to the range. 
GAS PRESSURE REGULATOR 
The gas pressure regulator supplied with this range must be used. The inlet 
pressure to the regulator should be as follows for proper operation: 
Natural gas  LP gas 
Minimum pressure  5" WC  10" WC 
Maximum pressure  7" WC  13" WC 
Contact local gas supplier if you are not sure about the inlet pressure. 
Burner Input Requirements 
Input ratings shown on the model/serial/rating plate are for elevations up to 
2,000 ft (609.6 m). 
For elevations above 2,000 ft (609.6 m), ratings are reduced at a rate of 4% 
for each 1,000 ft (304.8 m) above sea level (not applicable for Canada). 