User guide

7. CERTIFICATION
Page 44 of 44
1. ATEX CERTIFICATE
2. US/CANADIAN CERTIFICATE
This product has been examined against the following standards
ATEX:
EN 60079-0:2009
EN 60079-2:2007
EN 60079-11:2007
EN 60529 (+A1):2000
US/CANADA:
FM3600 1998
FM3610 2010
FM3810 2005
FM3620: 2000
ANSI/NEMA 250: 1991
ANSI/IEC 60529: 2004
ANSI/NFPA-496: 2003
CSA-C22.2 No. 0.4: 1999
CSA-C22.2 No. 157: 2006
CSA-C22.2 No. 1010.1: 2004
CSA-C22.2 No. 60529: 2005
TYPE/MODEL
HAZARDOUS AREA PROTECTION DEGREE
CATEGORY
CERTIFICATE
SERIAL No.
POWER SUPPLY
Um:
PURGED ENCLOSURE VOLUME
MINIMUM PRE PURGE VOLUME
MINIMUM PURGE DURATION
MAXIUM ENCLOSURE LEAKAGE RATE
MINIMUM PURGE SUPPLY PRESSURE
MINIMUM PRE PURGE FLOW
MINIMUM FLOW DURING OPERATION
MIN. OVERPRESSURE DURING OPERATION
MAX. OVERPRESSURE DURING OPERATION
MAXIMUM PROCESS GAS FLOW
MAXIMUM PROCESS GAS PRESSURE
Flammable substance oxygen concentration must not exceed 2%.
Flammable substance shall not have a UEL higher than 80%.
: WIM 9610
: CLASS I, DIV2, GROUPS B, C & D
: TYPE Z - PURGE
: T3C, TA = +5C TO +45C
TYPE 4X (US), IP66
: XXXX
: 115Vac, 60Hz, 12A /
: 230Vac, 50Hz, 6A, +/-10%
: 250 Vrms / Vdc maximum
: 92.5 liter
: 462.5 liter
: (8 minutes)
: 1 liter / second
: 4 barG
: 2.8 liter / second
: 0.5 liter / second
: 6 mbarG
: 10 mbarG
: 0.6 liter / minute
: 200 mbarG
84F HORSEBLOCK RD.
YAPHANK, NY 11980
U.S.A.
TEL: 1-631-345-3434
- THIS ENCLOSURE NORMALLY CONTAINS INSTRUMENT AIR AND
CAN RELEASE FLAMMABLE SUBSTANCES
- DO NOT OPEN THIS CABINET WHEN AN EXPLOSIVE ATMOSPHERE
IS PRESENT
- DO NOT USE THE OVERRIDE SWITCH WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
- TO PREVENT THE RISK OF ELECTROSTATIC SPARKING, THE VIEWING
PORT SHALL BE CLEANED ONLY WITH A DAMP CLOTH
WARNING
84F HORSEBLOCK RD.
YAPHANK, NY 11980
U.S.A.
TEL: 001-631-345-3434
- THIS ENCLOSURE NORMALLY CONTAINS INSTRUMENT AIR AND
CAN RELEASE FLAMMABLE SUBSTANCES
- DO NOT OPEN THIS CABINET WHEN AN EXPLOSIVE ATMOSPHERE
IS PRESENT
- DO NOT USE THE OVERRIDE SWITCH WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
- TO PREVENT THE RISK OF ELECTROSTATIC SPARKING, THE VIEWING
PORT SHALL BE CLEANED ONLY WITH A DAMP CLOTH
WARNING
1725
TYPE/MODEL
HAZARDOUS AREA PROTECTION DEGREE
CATEGORY
CERTIFICATE
SERIAL No.
POWER SUPPLY
Um:
PURGED ENCLOSURE VOLUME
MINIMUM PRE PURGE VOLUME
MINIMUM PURGE DURATION
MAXIUM ENCLOSURE LEAKAGE RATE
MINIMUM PURGE SUPPLY PRESSURE
MINIMUM PRE PURGE FLOW
MINIMUM FLOW DURING OPERATION
MIN. OVERPRESSURE DURING OPERATION
MAX. OVERPRESSURE DURING OPERATION
MAXIMUM PROCESS GAS FLOW
MAXIMUM PROCESS GAS PRESSURE
c) a restriction that the flammable substance oxygen concentration must not exceed 2%.
d) a restriction that the flammable substance shall not have a UEL higher than 80%.
: WIM 9610:
Ex ib px llC T3 Gb Ta=+5C to 45C, lP66.
: ll 2G
: FM11ATEX0006X
: XXXX
: 115Vac, 60Hz, 12A /
: 230Vac, 50Hz, 6A, +/-10%
: 250 Vrms / Vdc maximum
: 92.5 liter
: 462.5 liter
: (8 minutes)
: 1 liter / second
: 4 barG
: 2.8 liter / second
: 0.5 liter / second
: 6 mbarG
: 10 mbarG
: 0.6 liter / minute
: 200 mbarG
1.
2.
84F HORSEBLOCK RD.