User's Manual
File : CS-SUP-MUTI-WTHERMAPP-E01.sxw
7.7.3 Configuration of the alarms to be sent
The alarms to be sent are configured by writing to the parameter 0x22, or by sending the following
command :
Applicative
Command
Description
0x23 Request to configure the alarms to be sent
0xA3 Acknowledgement of the request
Contents of the request REQ_SEND_FRAME
Data Field (max : 152 bytes)
Applicative
command
Alarms Configuration byte
1 byte b7 b6 b5 b4 b3 b2 b1 b0
0x23 - - - -
Probe fault
detection
0 : deactivated
1 : activated
End of battery
life detection
0 : deactivated
1 : activated
High Threshold
detection
0 : deactivated
1 : activated
Low threshold
detection
0 : deactivated
1 : activated
When sending this command, the internal parameter relative to the configuration of the alarm
(0x22) will be automatically updated.
Contents of the response RECEIVED_FRAME
Data Field (max : 152 bytes)
Acknowledgement of
the applicative
command
Status
1 byte 1 byte
0xA3
0x00 : updating OK
0xFF : updating error
WaveTherm modules – application handbook page 62 of 65