User's Manual

File : CS-SUP-MUTI-WTHERMAPP-E01.sxw
7.4.5 Index logging once a week
This type of datalogging is used to log the index value for each input once a week. The time and day
of the week logging is carried out may be set with a parameter.
The parameters to be used, are the following :
Time of measurement (datalogging once a week, or once a month) (parameter 0x83)
Day of the week, or of the month (datalogging once a week, or once a month) (parameter 0x82)
These parameters must by initialized before activating the datalogging mode.
The format of the applicatives commands for reading and writing internal parameters, is described
in chapter 6.2.
Time of measurement (datalogging once a week, or once a month) (parameter 0x83)
This parameter allows to synchronize the periodic measurement. It is expressed in multiples of hour, and its
value must set from 0 to 23.
Day of the week, or of the month (datalogging once a week, or once a month) (parameter 0x82)
Value Day of the week
0 Sunday
1 Monday
2 Tuesday
3 Wednesday
4 Thursday
5 Friday
6 Saturday
Example : a user wants to log the temperature every monday, at 12:00 am.
Time of measurement (datalogging once a week, or once a month) (0x83) = 0x0C
Day of the week, or of the month (0x82) = 0x01
bits [b3:b2] of 'Operating Mode' byte (0x01) set to '10'
WaveTherm modules – application handbook page 44 of 65