User's Manual

File : CS-SUP-MUTI-WTHERMAPP-E01.sxw
7.3 WAKE-UP SYSTEM MANAGEMENT
In order to reduce module power consumption, a wake-up period parameter setting system is incorporated.
This system enables modification of the module wake-up period (default setting 1 s) by entering a time and
day of the week :
The wake-up period default value may be modified;
Two time-windows with different wake-up periods may be defined;
Each day of the week may be set in one of the following three cases :
Wake-up period default setting
Wake-up according to predefined time windows
No wake-up period (for safety reasons, the module is not disabled on reception and it
wakes up every 10 seconds)
7.3.1 Description of the parameters used
Parameter
number
Description
Size
(in bytes)
Access
rights
Default value
0x01 Operating mode 1 R/W
Depending of the
module used
(see 6.1.5)
0x02 Wake-up system status word 1 R/W 0x00
0x03 Default wake-up period (in s) 1 R/W 0x01
0x04 Start time for 1
st
time window (in hour) 1 R/W 0x07
0x05 Wake-up period - 1
st
time window (in s) 1 R/W 0x01
0x06 Start time for 2
nd
time window (in hour) 1 R/W 0x12
0x07 Wake-up period - 2
nd
time window (in s) 1 R/W 0x01
0x08 Enable time windows by day of week 1 R/W 0xFF
0x09 Enable wake-up periods by day of week 1 R/W 0x00
7.3.2 Choice of wake-up mode
These modes are directly dependant on the 'wake-up system status word' configuration and the values of
parameters associated with each mode.
Wake-up system status word
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
- - - - - -
Enable day-of-week selection
0 : disabled
1 : enabled
Enable time windows
0 : disabled
1 : enabled
Wake-up system
status word
Wake-up mode
0x00 Case n°1 : Periodic wake-up, without distinction of day of the week
0x01
Case n°2 : Periodic wake-up in specific time windows for certain days of the week, periodic wake-up
for the other days
0x02 Case n°3 : Periodic wake-up for certain days of the week, periodic wake-up disabled for the other days
0x03
Case n°4 : Periodic wake-up in specific time windows for certain days of the week, periodic wake-up
for some days and periodic wake-up disabled for the remaining days
Remark: before enabling a specific wake-up mode, the parameters associated with this mode must
first be set.
WaveTherm modules – application handbook page 37 of 65