User's Manual

File : CS-SUP-MUTI-WTHERMAPP-E01.sxw
Contents of request REQ_SEND_FRAME
Data Field (max : 152 bytes)
Applicative Command Precision level
1 byte 1 byte
0x01 (*)
(*) The precision field is used only for the modules :
- WaveTherm – PT100
- WaveTherm – PT1000
The WaveTherm – DALLAS doesn't support the precision capability. In this case the precision field
doesn't exist (size = 0 byte).
Thus, the format of the reponse varies according to the module used :
WaveTherm – DALLAS :
Contents of the response RECEIVED_FRAME
Data Field (max : 152 bytes)
Acknowledgement
of the Applicative
Command
Operating
Mode
Application
Status
MSB
Temperature
A
LSB
Temperature
A
MSB
Temperature
B
LSB
Temperature
B
1 byte 1 byte 1 byte 1 byte 1 byte 1 byte 1 byte
0x81 (*) (*) (*) (*)
(*) These fields are set only if the sensors are wired, and initialized, otherwise the returned value is 0x4FFF.
The format of the temperature is described in chapters 5.1.1 and 5.2.
WaveTherm – PT100 and WaveTherm – PT1000 :
Contents of the response RECEIVED_FRAME
Data Field (max : 152 bytes)
Acknowledgement
of the Applicative
Command
Operating
Mode
Application
Status
Temperature A
(Float 32 bits
LSB First)
Temperature B
(Float 32 bits
LSB First)
1 byte 1 byte 1 byte 4 bytes 4 bytes
0x81 (*)
(*) These fields are set only if the sensors are wired, otherwise the returned value is 0xFFFFFFFF.
WaveTherm modules – application handbook page 35 of 65