6.1.5 Definition of the module control bytes
Definition of the Operating Mode byte (0x01) :
MSB LSB
Operanting Mode
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
-
Threshold
Detection Mode
0 : successive mode
1 : cumulative mode
Low Threshold
Detection
0 : deactivated
1 : activated
High Threshold
Detection
0 : deactivated
1 : activated
Datalogging
00 : deactivated
01 : time steps
10 : once a week
11 : once a month
Stop Mode of the
Datalogging
0 : permanent loop
1 : stop memory full
-
Attention, it is advised the greatest prudence when modifying the parameter setting of the Operation
Mode variable. Indeed, the modifications on this variable generally requires the update of the associated
parameters.
Defautl value :
WaveTherm – DALLAS : 0x0A
WaveTherm – PT100 : 0x08
WaveTherm – PT1000 : 0x08
Definition of the Application Status byte (0x20) :
It is possible to reinitialize to zero the bits by a write to the Application Status parameter.
MSB LSB
Application Status
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Reset
detection
0: not
detected
1: detected
Low
Threshold of
sensor 2
0: not
detected
1: detected
High
Threshold of
sensor 2
0: not
detected
1: detected
Low
Threshold of
sensor 1
0: not
detected
1: detected
High
Threshold of
sensor 1
0: not
detected
1: detected
number of detected
sensors
0 : 0 or 1 sensor
detected
1 : 2 sensors detected
-
End of
battery life
0: not
detected
1: detected
Definition of the Extended Application Status byte (0x21) :
MSB LSB
Extended Application Status
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
- - - - - -
Probe fault on
sensor 2
0: not detected
1: detected
Probe fault on
sensor 1
0: not detected
1: detected
Remark : The probe fault bits are set only when a problem is detected on WaveTherm – PT100, and
WaveTherm – PT1000 probes.
WaveTherm modules – application handbook page 24 of 65